Technical data
6.1 Input
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
55
6EP3424-8UB00-0AY0
(12 V/20 A)
6EP3436-8UB00-0AY0
(24 V/17 A)
6EP3437-8UB00-0AY0
(24 V/40 A)
Input current at rated input
voltage 500 V
0.6 A
0.9 A
2.1 A
Inrush current limiting
(25 °C), max.
16 A
16 A
15 A
I
2
t, max
0.8 A
2
s
0.8 A
2
s
2.3 A
2
s
Integrated input fuse
None
None
None
Protection in the line feeder
cable (IEC 898)
Required: 3-pole, coupled
miniature circuit breaker
6 - 16 A characteristic C or
circuit breaker 3RV2011-
1DA10 (setting 3 A) or
3RV2711-1DD10 (UL489-
listed, DIVQ)
required: 3-pole, coupled
miniature circuit breaker
6 - 16 A characteristic C or
circuit breaker 3RV2011-
1DA10 (setting 3 A) or
3RV2711-1DD10 (UL489-
listed, DIVQ)
required: 3-pole, coupled
miniature circuit breaker
10 - 16 A characteristic C or
circuit breaker RV2011-
1DA10 (setting 3 A) or
3RV2711-1DD10 (UL489-
listed, DIVQ)
Figure 6-1
Power failure buffering