Technical data
6.2 Output
SITOP PSU8200/3800 3ph
58
Manual, 05.2018, C98130-A7638-A1-6-7629
6EP3446-8SB10-0AY0
(36 V/13 A)
6EP3446-8SB00-0AY0
(48 V/10 A)
6EP3447-8SB00-0AY0
(48 V/20 A)
Signaling
Relay contact (NO contact,
contact rating (isolated):
60 V DC/0.3 A) for "36 V
O.K."
Relay contact (NO contact,
contact rating (isolated):
60 V DC/0.3 A) for "48 V
O.K."
Relay contact (NO contact,
contact rating (isolated):
60 V DC/0.3 A) for "48 V
O.K."
Response when switching
on/off
No overshoot of U
out
(soft
start)
No overshoot of U
out
(soft
start)
No overshoot of U
out
(soft
start)
Starting delay, max.
2.5 s
2.5 s
2 s
Voltage rise, typ.
150 ms
150 ms
150 ms
Rise time of the output
voltage, max.
500 ms
500 ms
500 ms
Rated current I
out rated
13 A
10 A
20 A
Current range
•
Remark
0 - 13 A
60 ... 70 °C derating:
approx. 2 % I
out rated
/K
0 - 10 A
60 ... 70 °C derating:
approx. 5 % I
out rated
/K
0 - 20 A
22 A to 45 °C
60 ... 70 °C derating:
approx. 4 % I
out rated
/K
Active power output, typ.
468 W
480 W
1020 W
Constant overload current/for
a short circuit when powering
up, typ.
14 A
11 A
28 A
Short-time overload current
for a short circuit in opera-
tion, typ.
39 A
30 A
60 A
Duration of the overload
capability for an overcurrent
condition caused by a short
circuit in operation.
•
Remark
25 ms
per 1 min
25 ms
per 1 min
25 ms
per 1 min
Can be connected in parallel
to increase the power rating
•
Remark
Yes
Switchable characteristic
curve with switch A (see
and signaling (Page 15))
Yes
Switchable characteristic
curve with switch A (see
and signaling (Page 15))
Yes
Switchable characteristic
curve with switch A (see
and signaling (Page 15))
Number of devices that can
be connected in parallel to
increase the power rating,
units
2
2
2
Overload capability (Extra
Power)
19.5 A for 5 s/min
15 A for 5 s/min
30 A for 5 s/min
Output characteristic
(Page 62)
(Page 62)