Description, device design, dimension drawing
2.4 Status displays and signaling
SITOP PSU8200/3800 3ph
14
Manual, 05.2018, C98130-A7638-A1-6-7629
2.4
Status displays and signaling
6EP3436-8SB00-0AY0
(24 V/20 A)
6EP1437-3BA10
(24 V/40 A)
6EP3437-8SB00-0AY0
(24 V/40 A)
Operating display
⑤
LED green for "24 V O.K."
Yellow LED for overload in
"constant current" mode
Red LED for latching shut-
down in the "Shut down"
mode, for Remote OFF or for
overtemperature
(LED flashes)
LED green for "24 V O.K."
Yellow LED for overload in
"constant current" mode
Red LED for latching shut-
down in "shut down" mode
LED green for "24 V O.K."
Yellow LED for overload in
"constant current" mode
Red LED for latching shut-
down in the "Shut down"
mode, for Remote OFF or for
overtemperature
(LED flashes)
Signaling contact 13, 14
④
Relay contact (NO contact,
contact rating (isolated):
30 V AC/0.5 A, 60 V
DC/0.3 A, 30 V DC/1 A) for
"24 V O.K."
Relay contact (NO contact,
contact rating (isolated):
30 V AC/0.5 A, 60 V
DC/0.3 A, 30 V DC/1 A) for
"24 V O.K."
Relay contact (NO contact,
contact rating (isolated):
30 V AC/0.5 A, 60 V
DC/0.3 A, 30 V DC/1 A) for
"24 V O.K."
Remote contact 15, 16
④
Non-isolated input for remote
ON/OFF switching of the
power supply. Function: The
device is remotely switched
off when contacts 15, 16 are
short-circuited (R < 8
kΩ).
-
Isolated input for remote
ON/OFF switching of the
power supply.
Function: The device is re-
motely switched off when
contacts 15, 16 are short-
circuited (R < 8
kΩ).
6EP3446-8SB10-0AY0
(36 V/13 A)
6EP3446-8SB00-0AY0
(48 V/10 A)
6EP3447-8SB00-0AY0
(48 V/20 A)
Operating display
⑤
LED green for "36 V O.K."
Yellow LED for overload in
"constant current" mode
Red LED for latching shut-
down in the "Shut down"
mode, for Remote OFF or for
overtemperature
(LED flashes)
LED green for "48 V O.K."
Yellow LED for overload in
"constant current" mode
Red LED for latching shut-
down in the "Shut down"
mode, for Remote OFF or for
overtemperature
(LED flashes)
LED green for "48 V O.K."
Yellow LED for overload in
"constant current" mode
Red LED for latching shut-
down in the "Shut down"
mode or for Remote OFF
Signaling contact 13, 14
④
Relay contact (NO contact,
contact rating (isolated):
30 V AC/0.5 A, 60 V
DC/0.3 A, 30 V DC/1 A) for
"36 V O.K."
Relay contact (NO contact,
contact rating (isolated):
30 V AC/0.5 A, 60 V
DC/0.3 A, 30 V DC/1 A) for
"48 V O.K."
Relay contact (NO contact,
contact rating (isolated):
30 V AC/0.5 A, 60 V
DC/0.3 A, 30 V DC/1 A) for
"48 V O.K."
Remote contact 15, 16
④
Non-isolated input for remote
ON/OFF switching of the
power supply. Function: The
device is remotely switched
off when contacts 15, 16 are
short-circuited (R < 8
kΩ).
Non-isolated input for remote
ON/OFF switching of the
power supply. Function: The
device is remotely switched
off when contacts 15, 16 are
short-circuited (R < 8
kΩ).
Isolated input for remote
ON/OFF switching of the
power supply.
Function: The device is re-
motely switched off when
contacts 15, 16 are short-
circuited (R < 8
kΩ).