Uninterruptible 24 V power supply
To buffer the power supply, you need a (UPS1600) DC UPS module and a
(UPS1100) battery module in addition to the power supply units. Battery modules
are available with a choice of capacities ranging from 1.2 Ah to 12 Ah. You can
also use several battery modules of the same type to achieve higher capacities.
The intelligent battery management of the UPS1600 detects the connected
UPS1100 battery modules via the 2-wire "Energy Storage Link" line and ensures
optimum temperature-controlled charging.
The DC UPS module can be monitored in different ways:
•
Monitoring via Industrial Ethernet on the plant bus
•
Monitoring the signal contacts via the external peripherals
Below, we will describe configuration of both options in the SIMATIC Manager.
There is no difference between OS configuration of both variants.
5.1
UPS1600 on PROFINET IO field bus
You can parameterize the DC UPS module in the SIMATIC Manager using the
Generic Station Description. Monitoring of the DC USV on the OS is carried out
using product-specific function blocks that you can download for free from the item
entitled "
SITOP Library for SIMATIC PCS 7
Figure 5-1
OS Server
OS Client
Industrial Ethernet /
PROFINET IO
120/230V AC
AS
ET 200
SCALANCE
DC +24V
DC 24V GND
UPS1100
UPS1600
PSU8200
PSE202U
Switch
5.1.1
Setting up the hardware configuration
You configure the AS and the external peripherals according to the PCS 7
standard. To configure the SITOP UPS1600 uninterruptible power supply, the
corresponding GSD file must be installed.