4 Redundant 24 V DC power supply
Integration of a SITOP 24V power supply in PCS 7
Entry ID: 10948108, V3.2, 01/2019
26
S
iem
e
n
s A
G
2
0
1
9
A
ll r
igh
ts
re
se
rv
e
d
4.5
Creating a process picture
You need a process picture to visualize the status of the redundant power supply.
Proceed as follows:
1. Create a new process picture or open an existing one (1) in the folder of the
technological hierarchy in which the CFC plan that you edited before is located.
Figure 4-7
1
2. Execute the Compile OS function so that the system creates the process
variables and the messages in the OS project as well as the block icons in the
process picture.
3. Open the process picture using the WinCC Graphics Designer.
4. Draw the process picture as you want it to appear and position the block icons
(2) at the intended location in the picture.
5. Save the adapted process picture and close it.
Figure 4-8:
2