IO-Link 3SU14
12.2 Electronic modules for ID key-operated switches
SIRIUS ACT 3SU1 pushbuttons and signaling devices
334
System Manual, 08/2018, A5E03457306020A/RS-AK/010
12.2.6
Process image
Process image input (PII)
The process image input contains the most important status information of the electronic
modules for the ID key-operated switch for IO-Link.
Table 12- 5 PII - status information firmware version 1.4.0
DI (2 bytes)
PII
DI0.0
1: Ready
DI0.1
1: Group error
DI0.2
Reserved
DI0.3
Reserved
DI0.4
Reserved
DI0.5
Reserved
DI0.6
Reserved
DI0.7
Reserved
DI1.0
1: ID key recognized
DI1.1 - DI1.3
1: Authorization level
DI1.4 - DI1.6
1: Switch position
Table 12- 6 PII - status information as of firmware version 2.0.0
DI (2 bytes)
PII
DI0.0
Ready
DI0.1
Group error
DI0.2
Inserted ID key - Authorization level 1
DI0.3
Inserted ID key - Authorization level 2
DI0.4
Inserted ID key - Authorization level 3
DI0.5
Inserted ID key - Authorization level 4
DI0.6
Reserved
DI0.7
Reserved
DI1.0
ID key recognized
DI1.1
Digital output 0
DI1.1
Digital output 1
DI1.3
Digital output 2
DI1.4
Digital output 3
DI1.5
Digital output 4
DI1.6
Reserved
DI1.7
Reserved
In compatibility mode, the process image is identical to FW 1.4.0.