background image

2 Functions

26

  6MD665 Manual

C53000-G1876-C103-3

– interlocked (normal), or

– non-interlocked switching.

The   6MD665 is equipped with two key switches. The bottom switch is reserved for 
the switching mode. The "Normal" position allows interlocked switching while the 
"Interlocking OFF" position allows non-interlocked switching.

The following switching modes (remote) are defined:

• Remote or DIGSI

®

 commands (SC = LOCAL, REMOTE, or DIGSI)

– interlocked, or

– non-interlocked switching. Here de-interlocking occurs through a separate de-

interlocking job. The position of the key-switch is irrelevant.

– For commands from CFC (SC = AUTO SICAM), please observe the notes in the 

DIGSI CFC manual /3/ (block: BOOL after command).

Switching Mode (for devices without operator panel)

The dongle cable sets the switching mode of the device to "Normal". The specifica-
tions of the previous section apply.

Zone Controlled/Field Interlocking  

Zone controlled / field interlocking (e.g. via CFC) includes the verification that prede-
termined switchgear position conditions are satisfied to prevent switching errors (e.g. 
disconnector vs. earth switch, earth switch only if no voltage applied) as well as veri-
fication of the state of other mechanical interlocking in the switchgear bay  (e.g. High 
Voltage compartment doors).

Interlocking conditions can be programmed separately, for each switchgear, for device 
control OPEN and/or CLOSE.

The enable information with the data "switchgear is interlocked (OFF/NV/FLT) or 
enabled (ON)" can be set up,

• directly, using a single point or double point indication, key-switch, or internal indi-

cation (marking), or

• by means of a control logic via CFC.

The current status is queried for a control command and updated cyclically. The 
assignment is done via "Release object OPEN/CLOSE".

System interlocking

The system interlockings are then considered (allocation via central unit).

Double activation blockage  

Parallel switching operations are interlocked. On arrival of a command all command 
objects are tested which are also subject to the blockage, as to whether a command 
is current for them. While the command is being executed, the inhibit is in turn active 
for all other commands.

Device Status Check (scheduled = actual)  

For switching commands, a check takes place whether the selected switchgear is 
already in the scheduled/desired position (scheduled/actual comparison). This 
means, if a circuit breaker is already in the CLOSED position and an attempt is made 

Summary of Contents for SIPROTEC 6MD665

Page 1: ...SIPROTEC Bay Processing Unit 6MD665 V 4 2 Manual C53000 G1876 C103 3 3UHIDFH QWURGXFWLRQ 1 XQFWLRQV 2 QVWDOODWLRQ DQG RPPLVVLRQLQJ 3 7HFKQLFDO DWD 4 SSHQGL A LWHUDWXUH ORVVDU QGH ...

Page 2: ...serve the right to make technical improvements without notice Copyright Copyright Siemens AG 2002 All rights reserved Dissemination or reproduction of this document or evaluation and communication of its contents is not authorized except where expressly permitted All rights reserved particularly for the purposes of patent application or trademark registration Registered Trademarks SIPROTEC SINAUT ...

Page 3: ...ion on the System SIPROTEC 4 be desired or should partic ular problems arise which are not covered sufficiently for the purchaser s purpose the matter should be referred to the local Siemens representative Training Courses Individual course offerings may be found in our Training Catalogue or questions may be directed to our training centre in Nuremberg This product complies with the directive of t...

Page 4: ... injury or substantial property damage Only qualified personnel shall work on and around this equipment It must be thor oughly familiar with all warnings and safety notices of this manual as well as with the applicable safety regulations The successful and safe operation of this device is dependent on proper handling installation operation and maintenance by qualified personnel under observance of...

Page 5: ... for the options of the menus QGLFDWLRQVµ i e designators for information which may be output by the relay or required from other devices or from the switchgear are marked in a monospace type style in quotation marks Deviations may be permitted in drawings when the type of designator can be obviously derived from the illustration The following symbols are used in drawings device internal logical i...

Page 6: ...inactive at the same time Dynamic inputs edge triggered above with positive below with negative edge Formation of one analogue output signal from a number of analogue input signals Limit stage with setting address and parameter desig nator name Timer pickup delay T example adjustable with setting address and parameter designator name Timer dropout delay T example non adjustable Dynamic triggered p...

Page 7: ...Preface v 6MD665 Manual C53000 G1876 C103 3 Static memory RS flipflop with setting input S resetting input R output Q and inverted output Q ...

Page 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...

Page 9: ...ation Notes 11 2 1 2 2 Settings 12 2 1 3 Device General Settings 12 2 1 3 1 Description 12 2 1 3 2 Configuration Notes 15 2 1 3 3 Settings 15 2 1 3 4 Information 15 2 1 4 Statistics 16 2 1 4 1 Description 16 2 2 Command processing 17 2 2 1 General 17 2 2 1 1 Description 17 2 2 2 Control Device 17 2 2 2 1 Description 18 2 2 2 2 Information 19 2 2 3 Control Authorization 19 2 2 3 1 Description 19 2 ...

Page 10: ...es 38 2 4 6 3 Settings 39 2 4 6 4 Information 39 2 4 7 Measurement 3phase 1 packet 39 2 4 7 1 Description 39 2 4 7 2 Configuration Notes 40 2 4 7 3 Settings 40 2 4 7 4 Information 40 2 4 8 Measurement Aron 1 packet 41 2 4 8 1 Description 41 2 4 8 2 Configuration Notes 41 2 4 8 3 Settings 42 2 4 8 4 Information 42 2 5 Metered Value Processing 43 2 5 1 Description 43 2 6 Threshold Switch 49 2 6 1 De...

Page 11: ... 3 1 3 4 Mounting without operator panel 110 3 2 Checking Connections 112 3 2 1 Checking the data connections of the serial interfaces 112 3 2 2 Operating interface 112 3 2 3 Service Function interface 112 3 2 4 System interface 112 3 2 5 Termination 113 3 2 6 Time Synchronization Interface 113 3 2 7 Optical Fibers 114 3 2 8 Checking Power System Connections 114 3 3 Commissioning 117 3 3 1 General...

Page 12: ...sions 148 4 8 1 Housing for Panel Flush Mounting or Cabinet Installation 148 4 8 2 Mounting with detached operator panel or without operator panel 149 4 8 3 Detached Operator Panel 150 4 8 4 D SUB miniature Connector of Dongle Cable Panel Flush or Cubicle Door Cutout 151 A Appendix 153 A 1 Ordering Information and Accessories 154 A 1 1 Ordering Information 154 A 1 1 1 154 A 1 2 Accessories 156 A 2...

Page 13: ... Manual C53000 G1876 C103 3 A 5 Protocol Dependent Functions 169 A 6 Functional Overview 170 A 7 Settings 171 A 8 Information Lists 174 A 9 Group Alarms 187 A 10 Measured Values 188 Literature 195 Glossary 197 Index 205 ...

Page 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...

Page 15: ... 3 Introduction 1 The SIPROTEC Bay Processing Unit 6MD665 is introduced in this chapter The device is presented in its application characteristics and scope of functions 1 1 Overall Operation 2 1 2 Applications 5 1 3 Characteristics 7 ...

Page 16: ...ped with a powerful microprocessor system The device accomplishes all functions for controlling and monitoring of process components via the process bus Additionally measured values can be recorded and digitally processed by the Bay Processing Unit Hardware structure Figure 1 1 Hardware structure of the Bay Processing Unit 6MD665 ...

Page 17: ...asured via the fourth voltage input Furthermore two measuring transducer inputs are available The analogue values are transferred further to the IA input amplifier group The input amplification IA stage provides high resistance terminations for the ana logue input quantities It consists of filters that are optimised with regard to bandwidth and processing speed The analogue to digital AD stage con...

Page 18: ...cation Communication with other SIPROTEC 4 devices which also have inter relay commu nication can occur via the serial interface to the optional on the device rear Com munication is achieved regardless of the connection to the central device SICAM SAS and a redundancy to the system interface A further interface is provided for the time synchronization of the internal clock via external synchroniza...

Page 19: ...tor ing The number of the operating equipment to be switched is limited by the binary inputs and outputs available in the device or the binary inputs and outputs allocated for the switch position indications Depending on the primary equipment being con trolled one binary input single point indication or two binary inputs double point indi cation may be used for this process The capability of switc...

Page 20: ...tance in process control and automation engineering with especially high per formance A profile has been defined for the PROFIBUS communication that covers all of the information types required for process control engineering The integration of the devices into the power automation system SICAM can also take place with this profile In addition standardised protocols in accordance with IEC 60 870 5...

Page 21: ...fibre optics Optional for direct communication between the devices regardless of their connec tion to the control center Battery buffered clock that can be synchronised with an IRIG B via satellite or DCF77 signal binary input signal or system interface command Commissioning aids such as connection check status indication of all binary inputs and outputs easy check of system interface and influenc...

Page 22: ... auxiliary power supply hardware and software Monitoring of communication including the evaluation of the number of faulty trans mission messages Inter relay commu nication Direct exchange of information between the SIPROTEC 4 devices even without a connection to the SICAM control centre An interlocked control is also possible if the connection to the control centre or the control centre itself is...

Page 23: ...n There are instructions for reporting setting values and formulae where required Additionally it may be defined which functions are to be used 2 1 General functions 10 2 2 Command processing 17 2 3 Message Processing 29 2 4 Measured value processing 30 2 5 Metered Value Processing 43 2 6 Threshold Switch 49 2 7 Circuit breaker synchronisation 50 2 8 Inter relay communication 69 2 9 Process bus li...

Page 24: ... processed by the 6MD665 There are no indications and corresponding settings functions limit values are not dis played Functions that are not needed can be hidden Note The available functions and default settings depend on the order variant of the device In this way the entries described in the parameter overview are only then visible under functional scope if the device was ordered with position ...

Page 25: ...d Measurement 1phase 1 packet 0 MU1P_2 Disabled Enabled Disabled Measurement 1phase 2 packet 0 MU1P_3 Disabled Enabled Disabled Measurement 1phase 3 packet 0 MU3P_1 Disabled Enabled Enabled Measurement 3phase 1 packet 0 MUAron_1 Disabled Enabled Disabled Measurement Aron 1 packet 0 Synchronizing 1 Disabled Enabled Disabled Synchronizing Function 1 0 Synchronizing 2 Disabled Enabled Disabled Synchr...

Page 26: ...witched on and off with DIGSI via the operator interface or the service interface Indications of the device Device OK Indication The device is ready for operation The life contact is switched ON and the error LED is switched OFF with this message Value ON Reset Device Indication The device has performed a startup Special communication indication It is announced on the PROFIBUS that the SIPRO TEC V...

Page 27: ...sion blockage is per formed in the control center Value ON OFF DataStop Predefined binary input for tagging DWD6WRSµ Value ON OFF Test mode This operating mode is used for device tests during commissioning or maintenance In test mode all information in monitoring direction is marked with UBF test bit This procedure serves to avoid that events caused by the test mode initiate unwanted reac tions ho...

Page 28: ...OFF the test is ended i e the device is either operative again or the new parameters have been saved permanently or no parameter check is current Level 2 change The indication is issued as ON as soon as the parameter set loaded via DIGSI was changed by an online parametrisation and the device operates with these new param eters The indication is OFF as long as the parameter set loaded via DIGSI is...

Page 29: ...cription 401 T Backlight on 1 60 min 10 min Time Backlight on 402 DIGSI backplane Disabled Port C Port D Disabled Serviceport for DIGSI No Message Type of Information Description Light on EM Back Light on DataStop IE Stop data transmission Test mode IE Test mode HWTestMod IE Hardware Test Mode SynchClock IE_W Clock Synchronization Error FMS1 AM Error FMS FO 1 Error FMS2 AM Error FMS FO 2 3 Time Sy...

Page 30: ...ue window and or allocated to the system interface and thereby be transferred to higher level control centres Operating metered values from the process bus can be displayed in the default or control displays 110 Event Lost AM_W Event lost 125 Chatter ON AM Chatter ON 147 Error PwrSupply AM Error Power Supply 177 Fail Battery AM Failure Battery empty 183 Error Board 1 AM Error Board 1 184 Error Boa...

Page 31: ...re enabled A standard set of optional interlocking checks is provided for each command issued to circuit breakers switchgear 2 2 1 General The source of command are recorded in the event log at the moment of the command output 2 2 1 1 Description The following source of command are possible 2 2 2 Control Device Devices with integrated or detached operator panel can control switchgear via the opera...

Page 32: ... control command is issued During normal processing the control display indicates the new actual status after the control command was executed and the message FRPPDQG HQGµ at the lower display edge In case of control commands with feedback the message UHDFKHGµ is displayed for a short time before this If the selected control command is not accepted because an interlocking condition is not met then...

Page 33: ...l commands that are directly output to the switchgear to change their process state Switching commands for the control of circuit breakers unsynchronised discon nectors and ground electrodes Step commands e g raising and lowering transformer LTCs Setpoint commands with configurable time settings e g to control Petersen coils No Message Type of Information Description Q0 BR_D2 circuit breaker Q0 Q0...

Page 34: ...d path ensure that a switch command can be carried out only if the test of previously established criteria has been successfully com pleted In addition to general fixed prescribed tests for each resource separately further interlocks can be configured The actual execution of the command job also is then monitored The entire sequence of a command is described briefly in the follow ing Checking a co...

Page 35: ...extent of the interlocking checks is determined by configuration Switching objects that require system interlocking in a central control system are assigned to a specific parameter inside the bay unit via configuration matrix In the level below the SICAM HV components there is no further interlocking available therefore the switching fault protection is distributed between the SICAM central device...

Page 36: ...s Device Status Check setpoint actual The switching command is rejected and an error indication is displayed if the circuit breaker is already in the set position If this check is enabled then it applies whether switch interlocking is activated or deactivated System Interlocking For checking the system interlocking a locally issued command to the central unit is instigated with switching authority...

Page 37: ...t have the same virtual device number with REMOTE switching authority Switch commands of the remote control are rejected REMOTE switching authority A remote control command command with initiator source REMOTE is only allowed if the Key Switch for devices without key switch via configuration is set to REMOTE Figure 2 2 Standard interlocking arrangements 1 Initiator source REMOTE also includes LOCA...

Page 38: ...ck or enable LOCAL control but not remote or DIGSI commands The 6MD665 is equipped with two key switches The top switch is reserved for the switching authority The condition LOCAL allows com mands from the user interface of the relay The position REMOTE enables remote control The Switching authority DIGSI is used for interlocking and allows commands to be initiated using DIGSI Commands are allowed...

Page 39: ... operator panel The dongle cable sets the switching authority of the device to REMOTE The speci fications of the previous section apply Switching Mode for devices with operator panel The switching mode determines whether selected interlocking conditions will be acti vated or deactivated at the time of the switching operation The following switching modes local are defined Local commands SC LOCAL C...

Page 40: ...if no voltage applied as well as veri fication of the state of other mechanical interlocking in the switchgear bay e g High Voltage compartment doors Interlocking conditions can be programmed separately for each switchgear for device control OPEN and or CLOSE The enable information with the data switchgear is interlocked OFF NV FLT or enabled ON can be set up directly using a single point or doubl...

Page 41: ...Job command to object Switching mode REMOTE ON Job switching command to switchgear Derived command via CFC automatic command SC Auto SICAM Behaviour configured in the CFC block BOOL to command 2 2 3 2 Information 2 2 4 Process Data During the processing of the commands independent of the further message routing and processing command and process feedback information are sent to the message process...

Page 42: ...feed back information for all commands At the same time the command is sent the moni toring time is started monitoring of the command execution This time controls whether the device achieves the required final result within the monitoring time The monitoring time is stopped as soon as the feedback information arrives If no feedback information arrives a response Timeout command monitoring time app...

Page 43: ...ion All LEDs and binary outputs indicating specific messages can be freely configured The relay is delivered with a default setting The Appendix of this manual deals in detail with the delivery status and the allocation options The output relays and the LEDs may be operated in a latched or unlatched mode each may be individually set The latched conditions are protected against loss of the auxiliar...

Page 44: ...ch form various operands from the current and voltage input quantities 2 4 1 Measurement The Measured values parameter group is used for compiling the user defined mea sured values These measured values are created via DIGSI CFC or arrive via inter relay communication Usecases Limit measured values are used to indicate when a measured value recorded as the operational measured value has exceeded t...

Page 45: ...llowing chapters Table 2 3 Connection examples for a rated transformer voltage Vn secondary from 100 V Connection variants Input voltages Secondary Functions Parameter Transformer Vn sec Comments Star connection 3 x VfeederPh N 57 7 V 1 x VPh N 57 7 V Measuring trans ducer 3 phase 100 V for feeder operational measurements Measuring trans ducer 1 phase 100 V for reference operational measurements S...

Page 46: ...h an example using the function block Measuring transducer 3 phase Selecting the func tional scope First select the measuring transducer blocks from the DIGSI Functional scope dialog box which are to be contained in the functional scope of the device For this purpose open the device and click Functional scope in the function selec tion Select the available entry on the Measurement 3phase 1 packet ...

Page 47: ...t the values of parameters Secondary Voltage Nominal Value 0 00 V to 200 0 V and Secondary Current Nominal Value 0 00 A to 5 00 A depending on your requirements Figure 2 5 Dialog box for setting the parameters Allocating a measuring transducer Following configuration the inputs and outputs of the activated measuring transformer block in the allocation matrix of DIGSI are interconnected and the pro...

Page 48: ...the Object properties dialog box via the Properties context menu Select the Measured value description tab and make the settings The Measured value description tab is not relevant for the information items MP1_PHI phase angle MP1_WLF active power factor und MP1_BLF reactive power factor and therefore not available Figure 2 6 Object properties dialog box Measured value description tab Select the Tr...

Page 49: ...ansmission threshold tab Configure the object properties of the phase angle 3P1_PHI Figure 2 8 Object properties dialog box Transmission threshold tab Allocate the information item 3P1_PHI to C CFC as the destination and then link this in the corresponding CFC chart Figure 2 9 Example 3P1_PHI link in CFC chart ...

Page 50: ...cription The frequency of the voltage is determined from the input signal If the secondary input voltage on the device falls below 10 Veff the frequency is marked as invalid The over flow occurs when the secondary input voltage on the device exceeds 120 Veff The rated value of the frequency is taken from 3 6 VWHP DWD Routing of the measurement input to the respective measured value channel Voltage...

Page 51: ...he routing of the measuring results is performed with DIGSI Specifications for secondary transformer current are made in the properties dialog box of 08 B Information on allocation can be obtained from the SIPROTEC system description 1 2 4 5 2 Configuration Notes 6HF XUU1RP9DO The secondary factory preset rated transformer current can be set in the predefined range 2 4 5 3 Settings Addr Parameter ...

Page 52: ...hase voltage If the secondary input voltage on the device falls below 10 Veff the frequency is marked as invalid The over flow occurs when the secondary input voltage on the device exceeds 120 Veff The rated value of the frequency is taken from 3RZHU 6 VWHP DWD Routing of the measurement inputs to the respective measured value channels Phase current and Phase voltage and the routing of the measuri...

Page 53: ...applied at the output of the measuring transducer The frequency is determined from the applied phase voltage UL1 If the secondary input voltage on the device falls below 10 Veff the frequency is determined from the phase voltage UL2 or UL3 If all three voltages are too low the rated frequency is used as frequency In this case the combined variables and the frequency itself are marked invalid The p...

Page 54: ... secondary transformer voltage 2 4 7 2 Configuration Notes 6HF9ROWJ1RP9DO The factory preset rated transformer voltage can be set in the predefined range 6HF XUU1RP9DO The secondary factory preset rated transformer current can be set in the predefined range 2 4 7 3 Settings 2 4 7 4 Information Addr Parameter Setting Options Default Setting Description 0 SecVoltgNomVal 0 00 200 00 V 0 100 00 V Seco...

Page 55: ...equency is determined by means of the UL1L3 voltage If both voltages are too low the rated frequency is used as fre quency In this case the combined variables and the frequency itself are marked invalid The phase to phase voltages and the zero variables start to fluctuate depend ing on the deviation from the rated frequency The rated value of the frequency is taken from 3RZHU 6 VWHP DWD Routing of...

Page 56: ...rmation Description A1Input_U1 MK A1 Voltage Input U1 A1Input_U2 MK A1 Voltage Input U2 A1Input_I1 MK A1 Current Input I1 A1Input_I2 MK A1 Voltage Input I2 A1_U12 MW A1 Phase to Phase Voltage U12 A1_U13 MW A1 Phase to Phase Voltage U13 A1_I2 MW A1 Phase Current I2 A1_I3 MW A1 Phase Current I3 A1_P MW A1 Active Power P A1_Q MW A1 Reactive Power Q A1_S MW A1 Apparent Power S A1_ϕ MW A1 Phase Angle P...

Page 57: ... operating metered value which cannot be used for adjustment Table 2 4 Operating metered values The following types of information can be allocated to a metered value window in the DIGSI allocation matrix Metered values calculated from measured values Pulse metered value The same operations are possible with pulse and metered values calculated from measured values e g reset to set back to a specif...

Page 58: ...alue The properties of the pulse metered values can be configured via a dialog box Right click on the information item PulseMV in the Information column Display text in the allocation matrix Select Properties from the context menu The Object properties dialog box is opened Select the tab Measured value description and enter the unit kWh and the desired number of decimal places Enter the value whic...

Page 59: ... selecting one of the two options Figure 2 13 Object properties dialog box Restore trigger and energy flow direction tab Select the tab Pulse type and error input and make your settings there Select the Wiping pulse S0 option if the rising edge of a single pulse is to increment the metered value by one Select the Double current pulse option if the falling edge of a double current pulse is to incre...

Page 60: ...r MVMV under Power Meter PowerMeter Figure 2 15 Selecting information type measured value metered value Drag the selected information type with the left mouse button into the MU3P_1 group in the allocation matrix Allocating metered values calculated from measured values Allocate the inserted information item to the source Measured value in the allocation matrix and select 3P1_P from the list Alloc...

Page 61: ...the calculated value 0 0635 into the Conversion factor input box 3811 MW divided by 60 000 Figure 2 16 Object properties dialog box Restore trigger and energy flow direction tab Select the tab Restore trigger and energy flow direction and enter the restore trigger and energy flow direction Select the Cyclic option if the metered value is to be transmitted to the control center at cyclic intervals ...

Page 62: ...2 Functions 48 6MD665 Manual C53000 G1876 C103 3 Figure 2 17 Object properties dialog box Restore trigger and energy flow direction tab Accept the settings with OK ...

Page 63: ...figuration matrix You can set the central thresh old configured threshold and switching object in the object properties of the mea sured value tab Transmission threshold Use central threshold 10 Select this check box to use the factory preset threshold value of 10 This de activates all the other input and output options in this tab Parameterised threshold Set the desired value in this rotating box...

Page 64: ...e mea sured values from the process bus are RMS values and therefore cannot be used for synchronisation If the synchronisation function of the device is active the device can check whether the synchronisation conditions of both subnetworks are fulfiled synchrocheck when the circuit breaker is closed The device distinguishes between synchronous and asynchronous networks and reacts differently on th...

Page 65: ...three pin short or long interruption The synchronisation function ensures that the connection is only performed if both subnetworks are synchronous to each other or the deviation is within the defined limits The connection is performed if the following conditions are met at the moment of establishing the isolated connection Voltage magnitudes 8PLQ V 8PD Difference of voltage magnitudes V 8PD Frequ...

Page 66: ...of the reference and feeder voltage must be assigned to each synchronisation module individually Voltage application If the voltage application is used the user must set a switching sequence with the fol lowing components Voltage application Synchronisation Voltage deselection The voltage application option ensures that a 250 ms delay is considered in the mea suring algorithm after the synchronisa...

Page 67: ...es the measuring phase of 6 0HDVµ Measurement request start of measurement to 6 QF ORVH5HOµ switching release Command process ing phases with synchrocheck Depending on the setting and the current process condition the individual phases of the command processing are executed skipped or the command processing is aborted When integrating the synchronisation procedure into a switching sequence the des...

Page 68: ... check phase SYNC function module selection Table 2 6 Start conditions check phase operating mode analysis Measuring This phase executes the synchronisation subfunction This phase is coordinated by means of input indications 6 0HDVµ start stop of measurement 6 GLU 2µ bypassing 6 EORFNµ block switching enable Number of SYNC function blocks including the control device to be switched Number of input...

Page 69: ... Input indications and output indications of the synchronisation function Table 2 7 Controlling the measuring phase Action Measuring Reaction Sy1 Meas ON and Sy1 dirCO ON and Sync block OFF Switching enable Sync CloseRel ON Sy1 Meas ON and Sy1 dirCO OFF Start Sy1 Meas OFF Stop Synchronisation conditions reached or Sy1 dirCO ON and Sync block OFF Stop Switching enable Sync CloseRel ON Synchronisati...

Page 70: ...true for an abort of the command proce dure Voltage deselection The voltage application action must be terminated This is also true for an abort of the command procedure Interfaces The following data are relevant for the user as an interface Commands Commands to the circuit breaker the function from different initiators Input indications Indications for controlling the synchronisation function Out...

Page 71: ...d as often as synchronisation settings groups are required Code Explanation Command ON OFF to SyncSD Control command from different initiators ON Control command for switching the control device on with or without synchronisation procedure OFF Control command for switching the control device off with out synchronisation procedure Command abort to SyncSD or to all Abort command a running command pr...

Page 72: ... exe cuted but a switching enable is prevented The blocking of the switching enable is signalled via the Sync block output indication ON switching enables are blocked OFF switching enables are provided Sy1 dirCO Bypassing The measuring function is bridged i e a measurement for Sy1 block OFF immediately initiates a switching enable ON The measuring function is skipped or stopped with Sy1 Meas ON Th...

Page 73: ...he difference voltage amount is greater than the setting The corresponding SVK_Udiff measured value indication is transmit ted additionally Sync fdiff The difference voltage amount is greater than the setting The corresponding SVK_Fdiff measured value indication is transmit ted additionally Sync α diff The amount of the difference angle is greater than the setting The corresponding SVK_Fdiff measu...

Page 74: ...ults of imprecise primary transformers can also be cor rected The phase angle can be set in the predefined range A default value is preset Sync U1 The U1 voltage is smaller than the Vmin setting The corresponding SVK_Usyn1 measured value indication is trans mitted additionally provided that Dead Bus is not switched on or that no Dead Bus voltage was set Sync U2 The U2 voltage is greater than the V...

Page 75: ...on nected It can be specified in the predefined range A default value is preset 8PD The upper voltage limit 8PD specifies the maximum voltage which may be con nected It can be specified in the predefined range A default value is preset 8GHDG The voltage threshold indicates the voltage maximum up to which a line or busbar is detected as dead It can be specified in the predefined range A default val...

Page 76: ...et αGLII This parameter indicates the maximum angle difference between the voltages of the subsystems for which the connection is performed It becomes effective if the fre quency difference of the subsystems Df FdiffSyn is valid The angle can be set in the predefined range A default value is preset 7 6 1 521 This parameter indicates the switch delay time for synchronous systems This is the minimum...

Page 77: ...Synchronize to U1 and U2 0 Sync U1 U2 YES NO NO Synchronize to U1 and U2 0 UdiffSyn 0 5 40 0 V 2 0 V Maximum voltage difference syn chronous 0 fdiff 0 03 2 00 Hz 0 10 Hz Maximum frequency difference syn 0 αdiff 2 60 10 Maximum angle difference syn 0 UdiffAsyn 0 5 40 0 V 2 0 V Maximum voltage differnece asynchronous 0 f SYNCHRON 10 40 mHz 10 mHz Frequency diff treshold Sync Async 0 T SYNCHRON 0 00 ...

Page 78: ...c CloseRel AM Sync Release of CLOSE Command Sync Error AM Synchronization Error Sync block AM Sync blocked Sync MonTimeExc AM Sync Monitoring Time exceeded Sync synchron AM Sync Synchron Sync U1 U2 AM Sync Condition U1 U2 fulfilled Sync U1 U2 AM Sync Condition U1 U2 fulfilled Sync U1 U2 AM Sync Condition U1 U2 fulfilled Sync Vdiff AM Sync Voltage difference exceeded Sync fdiff AM Sync frequency di...

Page 79: ... 20 Specifying functional scope Configuring syn chronisation Click Synchronisation in the tree view of DIGSI The available synchronisation func tion groups are displayed in the list box under Function selection Double click the function group e g SYNC function group 1 which you would like to configure The dialog box for configuration is opened It contains the tabs System data General Asyn conditio...

Page 80: ...nctions 66 6MD665 Manual C53000 G1876 C103 3 Figure 2 21 Synchronization System data tab Make additional settings in the tabs General Asyn condition and Syn Condition Figure 2 22 Synchronization General tab ...

Page 81: ...the process bus In Bay Processing Unit 6MD665 the synchronous closing of circuit breakers can also occur via the process bus 2 7 4 1 Description Through the SICAM HV components and the process bus additional runtimes depen dent on the system configuration are caused in between the logical setting of the ON command up to the output at the contact of the DBC With the structure shown in the figure th...

Page 82: ...creased by the runtime of the ON command via the process bus in the System data tab A measurement is required for determining the runtime For synchronisation via the process bus select the relevant circuit breaker in the Properties of the SYNC function group in the General tab Note For safety reasons the maximum permissible frequency difference for the CB syn chronisation via the process bus is 10...

Page 83: ... process information via the serial IRC bus An application for the Inter relay communication could be the interlocking conditions within a bay with a 11 2 circuit breaker method operated with three bay controllers The OLM Optical Link Module interface modules required for an optical connec tion of the IRC user can be found in the accessory list in the Appendix Requirements Certain requirements mus...

Page 84: ...he devices occurs electrically via an RS485 interface The electrical connections are terminated with resistors at the ends first and last device which are set via jumpers in the 6MD665 device The jumper settings can be found in Chapter Installation and Commissioning One of the following operating modes can be selected in DIGSI using the serial inter face settings Table 2 14 Operating mode of the I...

Page 85: ...ng resistors are set with jumpers in the 6MD665 device and with DIL switches S1 switches 1 and 2 in the OLM The jumper settings can be found in Chapter Installation and Commis sioning The connection of the interface converters is optical in series and its operation is asynchronous A theoretical baud rate of 9600 Baud to 115200 Baud is set with a DIL switch S2 switch 5 off 6 on 7 on 8 off One of th...

Page 86: ...ns Insert SIPROTEC 4 device Objects of type SIPROTEC device are inserted into the project structure from the device catalog via drag and drop Right click an object of type Folder In the context menu click Insert new object SIPROTEC device The window Device catalog opens Alternatively click Device catalog in the context menu When selecting a device type note that this must be suitable for a Inter r...

Page 87: ...rface Click OK when you have defined the entire device model Proceed in a similar manner with the rest of the objects of type SIPROTEC device which are to be users of the IRC combination An object of type IRC combination is inserted with the DIGSI Manager The users of an IRC combination and the required transmission parameters are specified here Inserting an IRC combination The users of an IRC com...

Page 88: ...vices arrive at the other devices simul taneously The master repeats the slave query in case of faulty messages The number of repe titions is configurable A large number of repetitions with message errors or a poor connection extends the cycle time of the bus Only one repetition should be set for fibre optic connections After a connection failure the master attempts to establish a new connection a...

Page 89: ...ultiple selection Alternatively add or remove a SIPROTEC 4 device with a double click on its name in the appropriate box An IRC combination can comprise a maximum of sixteen users When this number has been reached a fault indication is displayed as soon as you want to add another SIPROTEC 4 device Specifying a master Each IRC combination requires a SIPROTEC 4 device as a master The first SIPRO TEC...

Page 90: ...s been defined in the device model These columns are shielded as soon as you select the information filter Only com mands This is explained by the fact that commands cannot be swapped within an IRC combination Allocable Information types The following information types can be allocated within an IRC combination Single point indication only SI not SI_F Double point indication only OI not OI_F Inter...

Page 91: ...4 device within an IRC combination with the device matrix You must decide what information is to be transmitted from which source device to which destination device and what information is to be created in the destination device by the information it has received Note The combination matrix is structured similarly to the device matrix The mechanisms e g to hide and show lines and column are identi...

Page 92: ...id ually in the device matrix Destination The destination designates the SIPROTEC 4 device to which information is for warded A destination column is shown in the combination matrix for each user device in an IRC combination Group A group represents the scope of information that a user of an IRC combination makes available to the other users A group is therefore shown in the combination matrix for...

Page 93: ...ble point indications and double point indications with fault positions Saving and terminat ing routings All your routings must be explicitly saved Click File Save as in the menu bar for this To close the combination matrix click File Exit in the menu bar Setting communication parameters for individual devices A special communication module must be installed in each SIPROTEC 4 device pro vided for...

Page 94: ...losed The parameter is not activated until the parameter set is updated Setting communication parameters for a combination While the slot to which this communications module is connected is the only setting which needs to be made in the device specific communication parameters several settings need to be taken into consideration for the combination as a whole The set tings which need to be made ar...

Page 95: ...you can choose between UART and HDLC HDLC ensures an approx 15 greater transmission density than UART using the same baud rate The selected transmission mode must be compatible with the communications modules installed in the SIPROTEC 4 devices in the IRC combination Baud rate Select a baud rate from this drop down list box Which baud rates are available for selection depends on the transmission m...

Page 96: ...s for a certain number of cycles To do this select a value between 0 and 254 in the drop down list box Minimum cycle time The cycle time defines the total duration of a cycle during which all slave devices are queried by the master device Select a value between 10 and 10 000 ms from the spin box As the length of the cycle time depends on the capacity of the master the cycle time actually achieved ...

Page 97: ...been issued these parameter sets are updated one after the other However it is important for you to know after which modification which SIPRO TEC 4 device needs to be reinitialised Here is a brief overview Changing the slot for the communications module parameter set of the user con cerned Modification of a serial interface setting on the tab Transmission parameters parameter sets of all users Mod...

Page 98: ... IRC combination including the clas sification letters of the selected slots Update information for each individual user in the IRC combination Right click an object of type IRC combination Click Delete Object contents in the context menu The Print Combination Information dialog box opens Figure 2 36 Print combination information dialog box Specifying the scope of printing You specify the scope of...

Page 99: ...as the mouse cursor is in the display area When you do this the display of the print page is also zoomed in defined stages Click Zoom out to zoom out the display of the print page in defined stages This button is inactive as soon as the smallest possible display size has been reached Note An enlarged or shrunken view has no influence on the print results Printing information Click Print to print t...

Page 100: ... 86 6MD665 Manual C53000 G1876 C103 3 Select the entry Inter relay communication from the Time synchronization source list box and confirm the entry with OK Figure 2 38 Time synchronization time format dialog box ...

Page 101: ...eterisation tools carry out an export of the parameterised information from ModPara to DIGSI so that the process information of the submod ules SICAM HV can be converted into process objects of the SIPROTEC 4 device 6MD665 For a file transfer the Process Communication Unit PCU submodule structure is to be illustrated in a two level directory tree in the parameter set of the SIPROTEC 4 device 6MD66...

Page 102: ...linked with which device interface It may also be determined which properties the information and the interfaces should have During allocation indications and statistical values of previous events can be lost Therefore the operational indication buffer and the sta tistic meter should be read out before alterations are made later on Configuring process bus After you have inserted a process control ...

Page 103: ... the option Process bus link from the drop down list box Configuration Then click Set The dialog box Configure process bus opens Figure 2 41 Configuring process bus Assigning HV project description If a path to a project description file is not shown in the box HV project description click Assign The Open dialog box is displayed ...

Page 104: ...which have already been assigned to other process control devices may no longer be contained in the new project description file In this event a corresponding message is displayed in the dialog box Configure process bus Figure 2 43 Assigning project description Assigning HV field description The names of all the fields declared in the selected project description file are now shown in the drop dow...

Page 105: ...ly below this one represents a PCU Objects for the submodule are arranged below a PCU Displaying properties Select the Ethernet connection of the PCD and click Properties The Properties Ethernet connection of the PCD window is opened The displayed station number and the two displayed addresses are created by DIGSI Manager and cannot be changed Figure 2 45 Properties of Ethernet connection of PLG C...

Page 106: ...f field description information are displayed in the tab Process bus import Figure 2 47 Process bus import report All relevant field information is now saved in the parameter set of the SIPROTEC 4 device Allocating informa tion of PCUs Information of the PCUs is allocated with the allocation matrix in the DIGSI operating program Double click the Allocation object in the data window For each PCU on...

Page 107: ...eived via the process bus are identified as external indica tions The information objects are created by importing the data from ModPara or are copied from the DIGSI information catalogue Commands to the process bus Commands to the process bus are commands which are forwarded to the process bus after having passed a command check The command procedure is monitored com pletely in 6MD665 As the comm...

Page 108: ...lso possible with the process control device via the available 7 command contacts In general you direct single commands for signal ling here cabinet lamp horn Directing switchgear as with the SIPROTEC 4 bay controllers is also possible Additional information can be obtained from the SIPRO TEC system description 1 ...

Page 109: ...ol systems They must be familiar with applicable safety rules safety regulations and the operation of a power system Hardware mod ifications that might be needed in certain cases are explained Some of the tests require the protected line or equipment to carry load 3 1 Installation and Connections 96 3 2 Checking Connections 112 3 3 Commissioning 117 3 4 Final Preparation of the Device 125 ...

Page 110: ...em Manual The compliance these data is verified with the power system data Connection vari ants Connection examples for the current and voltage transformer circuits are given in the Appendix Currents Voltages As the voltage inputs of the 6MD665 device have an operating range from 0 to 170 V this means that phase phase voltages can be assessed up to 3 170 V 294 V Binary inputs and outputs The confi...

Page 111: ...cer packets Control voltage for binary inputs In the delivery status the binary inputs are set in a way ensuring that a direct current equalling the supply voltage is set as control variable If the rated values differ from the power system control voltage it may be necessary to change the switching threshold of the binary inputs To change the switching threshold of a binary input a jumper must be ...

Page 112: ...rinted circuit boards such as checking or moving switching elements or exchanging modules proceed as follows Prepare area of work Provide a grounded mat for protecting components subject to damage from electrostatic discharges ESD The following equipment is needed screwdriver with a 5 to 6 mm wide tip 1 Philips screwdriver 5 mm socket or nut driver On the rear panel remove the studs of the submini...

Page 113: ...d the bottom latch down so that the plug connector of the ribbon cable is pressed out These activities are not necessary if the device has a detached operator panel However on the CPU processor module 1 the 7 pin plug connector X16 behind the subminiture socket and the plug connector of the ribbon cable connected to the 68 pin plug connector on the rear side must be removed Disconnect the plug con...

Page 114: ... and Commissioning 100 6MD665 Manual C53000 G1876 C103 3 Module arrange ment 6MD665 with measured values Figure 3 2 Front view with measured values after removal of the front cover simplified and with minimised zoom ...

Page 115: ...s BI1 to BI8 using the layout of the PCB of the input output module I O 1 and the tables below Figure 3 3 I O 1 input output module with representation of the jumpers required for checking the settings Table 3 1 Jumper setting of the rated voltage of the integrated power supply on the input output module I O 1 Jumper Rated voltage 24 to 48 V DC 60 V DC 110 V DC 220 to 250 V DC X51 Not used 1 2 1 2...

Page 116: ...upply voltage DC 110 V 3 Factory settings for devices with rated supply voltages of 220 V DC to 250 V DC Jumper Open in the quiescent state Closed in the quiescent state Presetting X40 1 2 2 3 2 3 Binary Input Jumper Threshold 17 V1 Threshold 73 V2 Threshold 154 V3 BI1 to BI8 X21 X22 1 L 1 L 2 M 2 M 3 H 3 H BI1 to BI8 X23 X24 1 L 1 L 2 M 2 M 3 H 3 H BI1 to BI8 X25 X26 1 L 1 L 2 M 2 M 3 H 3 H BI1 t...

Page 117: ...o X63 for each input transformer and addi tionally the common jumper X60 Figure 3 4 I O 5 input output module with representation of the jumpers required for checking the settings Jumpers X71 X72 and X73 on the I O 5 input output module serve for setting the bus address Their position may not be changed The table shows the factory setting of the jumpers The insertion slot of the module is describe...

Page 118: ...76 C103 3 Table 3 4 Module address jumper settings of input output modules I O 5 for Bay Pro cessing Unit 6MD665 3 1 2 4 Interface Modules Replacing inter face modules Figure 3 5 Processor module CPU with interface modules Jumper Position X71 2 3 X72 1 2 X73 2 3 ...

Page 119: ...resistors must be connected In the case of the 6MD665 these are variants with RS485 or PROFIBUS interfaces The termination resistors are connected to the corresponding PROFIBUS interface module that is mounted to the processor module CPU On delivery the jumpers are set so that the termination resistors are disconnected Both jumpers of a module must always be plugged in the same way Figure 3 6 Posi...

Page 120: ...s on the PROFI BUS interface module must be disconnected Figure 3 8 Termination of the RS485 interface external The R485 interface can be converted into an RS232 interface by modifying the setting of the appropriate jumpers The jumpers X5 to X10 must be plugged in the same way When the device is delivered from the factory the jumper setting corresponds to the configuration ordered and need not be ...

Page 121: ...r This action does not apply to the device version with detached operator panel Instead of this the connector of the ribbon cable derived from the 68 pin connector on the device rear panel must be plugged on the connector of the processor module CPU The 7 pin X16 connec tor belonging to the ribbon cable must be plugged behind the subminiature socket The plugging position is not relevant in this co...

Page 122: ...the screw thread fits in the hole of the lug Section 1 has pertinent information regard ing wire size lugs bending radii etc Figure 3 9 Panel flush mounting of a 6MD665 3 1 3 2 Rack Mounting and Cabinet Mounting To install the device in a frame or cubicle two mounting brackets are required The order numbers can be found in the Appendix Loosely screw the two mounting brackets in the rack or cubicle...

Page 123: ...the screw heads are even with the terminal block A ring lug must be centred in the connection chamber so that the screw thread fits in the hole of the lug The SIPROTEC system description 1 has perti nent information regarding wire size lugs bending radii etc Figure 3 10 Assembly of a 6MD665 in the rack or cabinet 3 1 3 3 Mounting with Detached Operator Panel Caution Be careful when removing or plu...

Page 124: ...ur covers Connect the ground on the rear plate of the operator control element to the protec tive ground of the panel using at least one M4 screw The cross sectional area of the ground wire must be equal to the cross sectional area of any other control con ductor connected to the device The cross section of the ground wire must be at least 2 5 mm 2 Connect the operator panel to the device Furtherm...

Page 125: ...cable at the device must always be plugged during oper ation For mounting the D subminiature connector of the dongle cable please observe the following Fasten the 9 pin socket of the dongle cable with the accompanying fastening parts according to the following figure example The dimensional diagram for the panel or cabinet cut out can be found in the Technical data section Plug the 68 pin connecto...

Page 126: ...A 1 for an ordering description of the cable 3 2 3 Service Function interface Check the data connection if the service is used to communicate with the device via hard wiring or a modem The same applies for the IRC connection 3 2 4 System interface When a serial interface of the device is connected to a central substation control system the data connection must be checked A visual check of the tran...

Page 127: ...us capable interfaces a termination is necessary at the bus for each last device i e termination resistors must be connected for RS485 or PROFIBUS interfaces The termination resistors are located on the RS485 and PROFIBUS interface module which is located on the CPU processor module If the bus is extended make sure again that only the last device on the bus has the terminating resistors switched i...

Page 128: ...t and for receive The normal setting of the character idle state for the fibre optic cable interface is Light off If the character idle state is to be changed use the operating program DIGSI as described in the SIPROTEC system description 1 3 2 8 Checking Power System Connections Before the device is energized for the first time the device should be in the final oper ating environment for at least...

Page 129: ...rounded properly Are the polarities of the current transformers the same Is the phase relationship of the current transformers correct Are the voltage transformers grounded properly Are the polarities of the voltage transformers correct Is the phase relationship of the voltage transformers correct Is the polarity for current input IE correct if used Is the polarity for voltage input UE correct if ...

Page 130: ...significant Transient move ment of the ammeter merely indicates the charging current of capacitors Remove the voltage from the power supply by opening the protective switches Disconnect the measuring test equipment restore the normal power supply con nections Apply voltage to the power supply Close the protective switches for the voltage transformers Verify that the voltage phase rotation at the d...

Page 131: ...power supply wait a minimum of 10 seconds before re energizing the power supply This wait allows the initial conditions to be firmly established before the device is re energized The limit values given in Technical Data Chapter 10 must not be exceeded neither during testing nor during commissioning When testing the device with secondary test equipment make sure that no other mea surement quantitie...

Page 132: ...U Process Communication Unit is to be checked This procedure is sketched out in Section Checking the process bus inter face 3 3 2 Test Mode and Transmission Block Activation and Deactivation If the device is connected to a central or main computer system via the SCADA inter face then the information that is transmitted can be influenced This is only possible with some of the protocols available se...

Page 133: ...erased If required these buffers should be extracted with DIGSI prior to the test The interface test is carried out Online using DIGSI Open the Online directory by double clicking the operating functions for the device appear Click on Test the function selection appears in the right half of the screen Double click on Testing Messages for System Interface shown in the list view The dialogue box Tes...

Page 134: ... sure that each checking process is carried out carefully without causing any danger see above and refer to DANGER Click on Send in the function to be tested and check whether the transmitted infor mation reaches the central station and shows the desired reaction With this proce dure the information beginning with which is normally coupled via binary inputs is also transmitted to the central stati...

Page 135: ...GSI in the online operating mode Open the Online directory by double clicking the operating functions for the device appear Click on Test the function selection appears in the right half of the screen Double click in the list view on Hardware Test The dialogue box of the same name opens see the following figure Structure of the Test Dialogue Box The dialog box is divided into three groups BI for b...

Page 136: ...lays is initiated all output relays are separated from the internal device functions and can only be operated by the hardware test function This means that e g a TRIP command coming from a protection function or a control command from the operator panel to an output relay cannot be executed Proceed as follows in order to check the output relay Ensure that the switching of the output relay can be e...

Page 137: ...s of the hard ware components which are current at this time are read in and displayed An update occurs for each hardware component if a command to change the condition is successfully performed for all hardware components if the Updatebutton is clicked for all hardware components with cyclical updating cycle time is 20 seconds if the Automatic Update 20sec field is marked Exiting the Test Mode To...

Page 138: ...mands sent to the circuit breaker can result in a trip close trip event of the circuit breaker by an external reclosing device Control from a Remote Control Centre If the device is connected to a remote substation via a system interface the corre sponding switching tests may also be checked from the substation Please also take into consideration that the switching authority is set in correspondenc...

Page 139: ...C system description 1 for more information on this The indication buffers are deleted under MAIN MENU Indications Delete Set so that in the future they only contain information on actual events and states see also 1 The counters in the switching statistics should be reset to the values that were existing prior to the testing see also SIPROTEC system description 1 Press the 6 key several times if ...

Page 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...

Page 141: ...nces may be exceeded The electrical and functional data for the maximum functional extent are fol lowed by the mechanical specifications with dimensional diagrams 4 1 General Device Data 128 4 2 Switchgear control 138 4 3 Circuit breaker synchronisation 139 4 4 User Definable Functions CFC 141 4 5 Operating measured values 144 4 6 Inter relay communication 146 4 7 Auxiliary functions 147 4 8 Dimen...

Page 142: ...recision 0 5 of measured value at 50 to 120 INom under reference conditions Secondary nominal voltage 80 V to 125 V Measuring range 0 V to 170 V Burden at 100 V Approx 0 3 VA Voltage overload capacity Thermal rms 230 V continuous Precision 0 5 of measured value at 50 to 120 VNom under reference conditions Input current 20 mA DC to 20 mA DC Overload capability 100 mA continuous Input resistance 10 ...

Page 143: ... AC DC converter Rated auxiliary DC Uaux 24 48 V DC 60 V DC Permissible voltage ranges 19 to 58 V DC 48 to 72 V DC Rated auxiliary DC Uaux 110 V DC 220 to 250 V DC Permissible voltage ranges 88 to 132 V DC 176 to 300 V DC Superimposed AC ripple voltage peak to peak IEC 60 255 11 15 of the auxiliary voltage Quiescent power consumption Approx 10 0 W Power consumption plus energised relay Approx 0 27...

Page 144: ...s Switching voltage 250 V Permissible current per contact inrush peak 5 A continuous 30 A 0 5 s Permissible current per contact On common path 5 A continuous 30 A for 0 5 s Life contact 1 with 1 NO contact or 1 NC contact switchable Switching capability ON 30 W VA Switching capability OFF 20 VA 30 W resistive 25 W at L R 50 ms Switching voltage 250 V Permissible current 1 A continuous Connection f...

Page 145: ...ibre 50 125 µm or using glass fibre 62 5 125 µm Permissible link signal attenuation Max 8 dB with glass fibre 62 5 125 µm Channel Distance max 0 93 mi 1 5 km Character idle state Configurable factory setting Light off Transmission Speed electrical HDLC 125 KBaud 250 KBaud 1 MBaud 1 25 MBaud UART 115 KBaud 250 KBaud optical HDLC 125 KBaud UART 500 KBaud isolated interface for data transfer RS485 Co...

Page 146: ...0 kB s 1738 824 ft 530 m IEC 60 870 5 103 RS485 isolated interface for data transfer to a control centre Connection Rear panel slot E 9 pin subminiature socket Test voltage 500 V 50 Hz Transmission Speed min 4800 Baud max 38400 Baud Factory setting 38400 Baud Channel Distance max 0 62 mi 1 km Fibre optic cable FO Type of Fibre Optic Link ST connector Connection Rear panel mounting location E Optic...

Page 147: ...ase at the double deck terminal on the case bottom Signal Nominal Voltages selectable 5 V 12 V or 24 V Signal Levels and Burdens Nominal Signal Voltage 5 V 12 V 24 V VIHigh 6 0 V 15 8 V 31 V VILow 1 0 V at IILow 0 25 mA 1 4 V at IILow 0 25 mA 1 9 V at IILow 0 25 mA IIHigh 4 5 mA to 9 4 mA 4 5 mA to 9 3 mA 4 5 mA to 8 7 mA RI 890 Ω at VI 4 V 1930 Ω at VI 8 7 V 3780 Ω at VI 17 V 640 Ω at VI 6 V 1700...

Page 148: ...ent Disturbance Variables Burst IEC 60255 22 4 and IEC 61 000 4 4 Class IV 4 kV 5 50 ns 5 kHz Burst length 15 ms rep etition rate 300 ms both polarities R i 50 Ω Test Duration 1 min High Energy Surge Voltages SURGE IEC 61 000 4 5 Installation Class 3 Impulse 1 2 50 µs Power Supply Voltage common mode 2 kV 12 Ω 9 µF diff mode 1 kV 2 Ω 18 µF Measuring Inputs Binary Inputs Relay Outputs common mode 2...

Page 149: ... mm Amplitude horizontal axis 1 Hz to 8 Hz 1 5 mm Ampli tude vertical axis 8 Hz to 35 Hz 1 g accelera tion Amplitude horizontal axis 8 Hz to 35 Hz 0 5 g acceleration vertical axis Frequency Sweep Rate 1 Octave min 1 cycle in 3 orthogonal axes Standards IEC 60 255 21 and IEC 60 068 Vibration IEC 60255 21 1 Class I IEC 60068 2 6 sinussoidal 5 Hz to 8 Hz 7 5 mm Amplitude 8 Hz to 15 Hz 2 g acceleratio...

Page 150: ...c compatibility EMC In addition the following is recommended All contacts and relays that operate in the same cubicle cabinet or relay panel as the numerical protective device should as a rule be equipped with suitable surge suppression components For substations with operating voltages of 100 kV and above all external cables should be shielded with a conductive shield grounded at both ends For su...

Page 151: ...tached operator panel 5 51 lb 2 5 kg International protection under IEC 60529 For equipment of the flush mount housing Front IP 51 Rear IP20 In flush mount case and in model with detached operator panel Front IP 51 Rear IP 50 For personal protection IP 2x with cover ...

Page 152: ...e position commands Single command double commands Pulse and continuous outputs Switching command to circuit breaker if wired directly to device 1 11 2 and 2 pin Programmable logic controller PLC logic graphic input tool Local Control Control via menu control control keys Assignment of function keys Remote control Using Communication Interfaces Using substation automation system e g SICAM Using DI...

Page 153: ...pickup value or 2 V Approx 0 9 V or 1 1 V max 1 V V measurements Quantity difference Tolerance 1 V to 40 V phase to phase 0 1 V increments 1 V Synchronous power conditions Φ measurement Tolerance 2 to 60 1 increments 2 f measurement Tolerance 0 03 Hz to 2 00 Hz 0 01 Hz increments 15 mHz The maximum permissible frequency difference depends on the circuit breaker operating time Max angle error 5 for...

Page 154: ... Synchronisation function delay after start 250 ms Maximum wait time max synchronisation duration 0 01 s to 600 00 s 0 01 s increments Tolerance of all times 1 of setting value or 10 ms Operating range Synchrocheck at rated frequency 50 Hz 2 Hz 60 Hz 2 Hz ...

Page 155: ... Double Point annunciation X X X CMD_CHAIN Switching sequence X X CMD_INF Command information X CONNECT Connection X X X D_FF D Flipflop X X X D_FF_MEMO status memory for restart X X X X DI_TO_BOOL Double Point to Boolean conversion X X X DIV division X X X X DM_DECODE Decode double point X X X X DYN_OR dynamic or X X X X LIVE_ZERO X LONG_TIMER Timer max 1193h X X X X LOOP Feedback loop X X X X LO...

Page 156: ...inputs of one chart for each task level number of unequal information items of the left border per task level 400 here the number of elements of the left border per task level is counted Since the same infor mation is indicated at the border several times only unequal information is to be counted Maximum number of switching sequences 20 Maximum number of time modules 20 corresponds to 18 long time...

Page 157: ...Processing 3000 PLC1_BEARB slow PLC processing 5000 PLC_BEARB fast PLC processing 1000 SFS_BEARB switchgear interlocking 3000 Element Number of TICKS Module basic requirement 5 Each input more than 3 inputs for generic modules 1 Connection to an input signal 6 Connection to an output signal 7 Additional for each chart 1 Switching sequence CMD_CHAIN 34 status memory for restart D_FF_MEMO 6 Feedback...

Page 158: ... to 120 S SNom Tolerance 0 5 of measured value at f fNom 5 Hz for U UNom and I INom 50 to 120 P real power in kW MW or GW primary and in PNom Range For cos Φ 0 707 to 1 00 Tolerance 0 5 of measured value at f fNom 5 Hz For U UNom and I INom 50 to 120 Q reactive power in kVAr MVAr or GVAr primary and in of QNom Range For sin Φ 0 707 bis 1 00 Tolerance 0 5 of measured value at f fNom 5 Hz For U UNom...

Page 159: ...id P Q S A phase voltage 0 1UNom or the nominal appara net power S 1 Power overflow range A phase current or a phase earth voltage in over flow Phase angle zero range are invalid sin ϕ cos ϕ and ϕ A phase voltage 0 1UNom or the nominal appara net power S 1 Frequency zero range is invalid f 45 Hz or a phase voltage 0 1UNom Frequency overflow range f 65 Hz Measured values technical data of the 20 mA...

Page 160: ... communication Number of users in the IRC combination Max 16 Number of information items which each IRC user can apply to the IRC bus Max 32 Minimum appearance duration for indica tions which are to be transferred via inter relay communication 20 ms due to IRC cycle time ...

Page 161: ...Binary input Communication Operating Modes for Time Tracking No Operating Mode Explanations 1 Internal Internal synchronization using RTC presetting 2 IEC 60870 5 103 External synchronization using system interface IEC 60 870 5 103 3 PROFIBUS FMS External synchronization using PROFIBUS inter face 4 Time signal IRIG B External synchronisation via IRIG B telegram format IRIG_B000 5 Time signal DCF77...

Page 162: ...nical Data 148 6MD665 Manual C53000 G1876 C103 3 4 8 Dimensions 4 8 1 Housing for Panel Flush Mounting or Cabinet Installation Figure 4 1 Dimensional drawing of a 6MD665 for panel surface and cabinet mounting ...

Page 163: ...ions 149 6MD665 Manual C53000 G1876 C103 3 4 8 2 Mounting with detached operator panel or without operator panel Figure 4 2 Dimensional drawing of a 6MD665 for surface mounting with without operator control unit ...

Page 164: ...4 Technical Data 150 6MD665 Manual C53000 G1876 C103 3 4 8 3 Detached Operator Panel Figure 4 3 Dimensional drawing of a detached operator panel ...

Page 165: ...6MD665 Manual C53000 G1876 C103 3 4 8 4 D SUB miniature Connector of Dongle Cable Panel Flush or Cubicle Door Cutout Figure 4 4 Dimensions of panel flush or cubicle door cutout of D SUB miniature connector of dongle cable ...

Page 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...

Page 167: ... show the proper connections of the devices to primary equip ment in many typical power system configurations Tables with all settings and all information available in this device equipped with all options are provided Default set tings are also given A 1 Ordering Information and Accessories 154 A 2 Terminal Assignments 158 A 3 Connection Examples 164 A 4 Default Settings 167 A 5 Protocol Dependen...

Page 168: ...onisation function 1 8 signal inputs 3 connected to common potential 5 not 12 one pin individual commands 6 connected to common potential 6 not 3 current transformers 4 voltage transformers transformer direct inputs 5 A rated current 2 measurement inputs 20 mA with synchronisation function 5 Power supply binary input pickup threshold setting Position 8 24 to 48 V DC binary input threshold 17 V 1 2...

Page 169: ... German language can be changed A Region World 50 60 Hz IEC ANSI language English language can be changed B Region US 50 60 Hz ANSI language American English language can be changed C System interface rear side port B Position 11 IEC 60870 5 103 protocol electrical RS485 2 IEC 60870 5 103 protocol optical 820 nm ST connector 3 Profibus FMS Slave electrical RS485 4 Profibus FMS Slave optical single...

Page 170: ...nal block type Order No 18 pin voltage terminal 12 pin current terminal C73334 A1 C31 1 12 pin voltage 8 pin current block C73334 A1 C32 1 Short circuit links Short circuit link for terminal type Order No 18 pin 12 pin voltage pin C73334 A1 C34 1 Current terminal 12 pin or 8 pin C73334 A1 C33 1 Socket housing Socket housing Order No 2 pin C73334 A1 C35 1 3 pin C73334 A1 C36 1 Mounting rails for 19...

Page 171: ...tion packages 7XS5402 0AA00 Display Editor Software for creating basic and mimic control pictures option package of the complete version of DIGSI Order No Display Editor 4 Full version with license for 10 PCs 7XS5420 0AA0 Graphic Tools Graphic Tools Order No Full version with licences for 10 comput ers 7XS5430 0AA0 DIGSI REMOTE 4 Software for remotely operating protec tive devices via a modem and ...

Page 172: ...nts A 2 1 Housing for panel surface and cabinet mounting 6MD6650 D E Figure A 1 General diagram 6MD665 D E panel flush mounting or cubicle installation with no measured values Interface D is also available with devices having the digit 5 in position 12 of the order number ...

Page 173: ... G1876 C103 3 6MD6651 D E 6MD6655 D E Figure A 2 General diagram 6MD6651 D E 6MD6655 D E panel flush mounting or cubicle installation with measured values Interface D is also available with devices having the digit 5 in position 12 of the order number ...

Page 174: ...using with detached operator panel 6MD6650 A C Figure A 3 General diagram 6MD665 A C panel surface mounting with detached opera tor panel with no measured values Interface D is also available with devices having the digit 5 in position 12 of the order number ...

Page 175: ...76 C103 3 6MD6651 A C 6MD6655 A C Figure A 4 General diagram 6MD6651 A C 6MD6655 A C panel surface mounting with detached operator panel with measured values Interface D is also available with devices having the digit 5 in position 12 of the order number ...

Page 176: ...using for installation without operator panel 6MD6650 F Figure A 5 General diagram 6MD665 F panel surface mounting without operator panel with no measured values Interface D is also available with devices having the digit 5 in position 12 of the order number ...

Page 177: ...000 G1876 C103 3 6MD6651 F 6MD6651 F Figure A 6 General diagram 6MD6651 F 6MD6655 F panel surface mounting without operator panel with measured values Interface D is also available with devices having the digit 5 in position 12 of the order number ...

Page 178: ...ction Examples Figure A 7 Transformer connections to a current transformer and a voltage transformer 1 phase measuring transducer packet Figure A 8 Transformer connections to 3 current transformers and 3 voltage transformers 3 phase measuring transducer packet ...

Page 179: ...n Examples 165 6MD665 Manual C53000 G1876 C103 3 Figure A 9 Transformer connections to 2 current transformers and 2 voltage transformers for an Aron connection and circuit breaker synchronisation connection with VLL ...

Page 180: ...alues for the synchronisation blocks 1 to 5 mea surement transducer connection in accordance with connection examples 1 and 2 Figure A 11 Connection of measured values for the synchronisation blocks 6 to 8 measure ment transducer connection in accordance with connection examples 1 and 2 ...

Page 181: ... 2 Binary Input Table A 2 Binary input presettings for all devices and ordering variants A 4 3 Binary Output Table A 3 Output relay presettings for all devices and ordering variants A 4 4 Function Keys Table A 4 Applies to all devices and ordered variants LED Annunciation No Remarks LED none Binary Input Annunciation No Remarks BI none Binary Output Annunciation No Remarks BO none Function Keys An...

Page 182: ...t display 6MD665 A 4 6 Pre defined CFC charts A CFC chart is already installed when the SIPROTEC 4 device is delivered Key switches Figure A 13 CFC chart keyswitches By interconnecting both DI_TO_BOOL blocks the Switching Authority function of both key switches of the device is implemented ...

Page 183: ... to VDEW no system interlock ing with local control Yes Yes setting tag gings without time stamp Time synchronisation Yes Yes Yes Commissioning aids Indicate measured value blocking Yes Yes No Create test indications DIGSI Yes Yes No Physical properties Transmission mode Cyclically Event Cyclically Event Cyclically Baudrate 4800 to 38400 Up to 1 5 MBaud Up to 1 25 MBaud Connection to device Electr...

Page 184: ...abled Measurement 3phase 1 packet 0 MUAron_1 Disabled Enabled Disabled Measurement Aron 1 packet 0 Synchronizing 1 Disabled Enabled Disabled Synchronizing Function 1 0 Synchronizing 2 Disabled Enabled Disabled Synchronizing Function 2 0 Synchronizing 3 Disabled Enabled Disabled Synchronizing Function 3 0 Synchronizing 4 Disabled Enabled Disabled Synchronizing Function 4 0 Synchronizing 5 Disabled ...

Page 185: ...00 sec 30 00 sec Maximum duration of synchronism check 0 fmin SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 95 105 95 Minimum frequency 0 fmax SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 95 105 105 Maximum frequency 0 SyncSD SYNC func...

Page 186: ...e for Synchroniza tion 0 Udead SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 1 60 V 5 V Voltage Treshold for Dead Line Dead Bus 0 Sync U1 U2 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 YES NO NO Synchronize to U1 and U2 0 Sync U1 U2 S...

Page 187: ...n 8 0 5 40 0 V 2 0 V Maximum voltage differnece asyn chronous 0 f SYNCHRON SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 10 40 mHz 10 mHz Frequency diff treshold Sync Async 0 T SYNCHRON SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 0 00...

Page 188: ... Buffers Configurable in Matrix IEC 60870 5 103 Event Log ON OFF Trip Fault Log ON OFF Trip Fault Log ON OFF Marked in Oscill Record LED Binary Input Function Key Binary Output Chatter Blocking Type Information Number Data Unit General Interrogation Light on Device General General func tions SP on off LED BI BO DataStop Device General General func tions IntSP on off LED BO 106 20 1 yes Test mode D...

Page 189: ...ntrol Device Command Pro cessing DM on off BI CB 240 164 1 yes Q9 Control Device Command Pro cessing BR_D2 on off BO 240 163 20 Q9 Control Device Command Pro cessing DM on off BI CB 240 163 1 yes ReleaseQ0 Control Device Command Pro cessing IntSP on off LED BO ReleaseQ1 Control Device Command Pro cessing IntSP on off LED BO ReleaseQ2 Control Device Command Pro cessing IntSP on off LED BO ReleaseQ8...

Page 190: ...41 202 1 yes Sync block SYNC function 1 Circuit breaker synchronisation OUT on off LED BO 41 204 1 yes Sync MonTimeExc SYNC function 1 Circuit breaker synchronisation OUT on off LED BO 41 205 1 yes Sync synchron SYNC function 1 Circuit breaker synchronisation OUT on off LED BO 41 206 1 yes Sync U1 U2 SYNC function 1 Circuit breaker synchronisation OUT on off LED BO Sync U1 U2 SYNC function 1 Circu...

Page 191: ...nc U2 SYNC function 1 Circuit breaker synchronisation OUT on off LED BO Sy2 eff SYNC function 2 SP on off LED BI BO Sy2 block SYNC function 2 SP on off LED BI BO Sy2 dirCO SYNC function 2 SP on off LED BI BO Sy2 Meas SYNC function 2 SP on off LED BI BO Sy2U1 U2 SYNC function 2 SP on off LED BI BO Sy2U1 U2 SYNC function 2 SP on off LED BI BO Sy2U1 U2 SYNC function 2 SP on off LED BI BO Sync CloseRe...

Page 192: ... U1 SYNC function 2 OUT on off LED BO Sync U2 SYNC function 2 OUT on off LED BO Sync U2 SYNC function 2 OUT on off LED BO Sy3 eff SYNC function 3 SP on off LED BI BO Sy3 block SYNC function 3 SP on off LED BI BO Sy3 dirCO SYNC function 3 SP on off LED BI BO Sy3 Meas SYNC function 3 SP on off LED BI BO Sy3U1 U2 SYNC function 3 SP on off LED BI BO Sy3U1 U2 SYNC function 3 SP on off LED BI BO Sy3U1 U...

Page 193: ... on off LED BO Sync f2 SYNC function 3 OUT on off LED BO Sync f2 SYNC function 3 OUT on off LED BO Sync U1 SYNC function 3 OUT on off LED BO Sync U1 SYNC function 3 OUT on off LED BO Sync U2 SYNC function 3 OUT on off LED BO Sync U2 SYNC function 3 OUT on off LED BO Sy4 eff SYNC function 4 SP on off LED BI BO Sy4 block SYNC function 4 SP on off LED BI BO Sy4 dirCO SYNC function 4 SP on off LED BI ...

Page 194: ...T on off LED BO Sync α diff SYNC function 4 OUT on off LED BO Sync f1 SYNC function 4 OUT on off LED BO Sync f1 SYNC function 4 OUT on off LED BO Sync f2 SYNC function 4 OUT on off LED BO Sync f2 SYNC function 4 OUT on off LED BO Sync U1 SYNC function 4 OUT on off LED BO Sync U1 SYNC function 4 OUT on off LED BO Sync U2 SYNC function 4 OUT on off LED BO Sync U2 SYNC function 4 OUT on off LED BO Sy...

Page 195: ... 5 OUT on off LED BO Sync U1 U2 SYNC function 5 OUT on off LED BO Sync Vdiff SYNC function 5 OUT on off LED BO Sync fdiff SYNC function 5 OUT on off LED BO Sync α diff SYNC function 5 OUT on off LED BO Sync f1 SYNC function 5 OUT on off LED BO Sync f1 SYNC function 5 OUT on off LED BO Sync f2 SYNC function 5 OUT on off LED BO Sync f2 SYNC function 5 OUT on off LED BO Sync U1 SYNC function 5 OUT on...

Page 196: ...ED BO Sync synchron SYNC function 6 OUT on off LED BO Sync U1 U2 SYNC function 6 OUT on off LED BO Sync U1 U2 SYNC function 6 OUT on off LED BO Sync U1 U2 SYNC function 6 OUT on off LED BO Sync Vdiff SYNC function 6 OUT on off LED BO Sync fdiff SYNC function 6 OUT on off LED BO Sync α diff SYNC function 6 OUT on off LED BO Sync f1 SYNC function 6 OUT on off LED BO Sync f1 SYNC function 6 OUT on of...

Page 197: ...nc Error SYNC function 7 OUT on off LED BO Sync block SYNC function 7 OUT on off LED BO Sync MonTimeExc SYNC function 7 OUT on off LED BO Sync synchron SYNC function 7 OUT on off LED BO Sync U1 U2 SYNC function 7 OUT on off LED BO Sync U1 U2 SYNC function 7 OUT on off LED BO Sync U1 U2 SYNC function 7 OUT on off LED BO Sync Vdiff SYNC function 7 OUT on off LED BO Sync fdiff SYNC function 7 OUT on ...

Page 198: ...nction 8 SP on off LED BI BO Sy8U1 U2 SYNC function 8 SP on off LED BI BO Sync CloseRel SYNC function 8 OUT on off LED BO Sync Error SYNC function 8 OUT on off LED BO Sync block SYNC function 8 OUT on off LED BO Sync MonTimeExc SYNC function 8 OUT on off LED BO Sync synchron SYNC function 8 OUT on off LED BO Sync U1 U2 SYNC function 8 OUT on off LED BO Sync U1 U2 SYNC function 8 OUT on off LED BO ...

Page 199: ...e General General func tions OUT on off LED BO 135 81 1 yes 55 Reset Device Device General General func tions OUT on LED BO 56 Initial Start Device General General func tions OUT on LED BO 106 5 1 60 Reset LED Device General General func tions OUT_E v on LED BO 106 19 1 67 Resume Device General General func tions OUT on LED BO 68 Clock SyncError Device General General func tions IntSP on off LED B...

Page 200: ...neral General func tions OUT on off LED BO 184 Error Board 2 Device General General func tions OUT on off LED BO 185 Error Board 3 Device General General func tions OUT on off LED BO 186 Error Board 4 Device General General func tions OUT on off LED BO 187 Error Board 5 Device General General func tions OUT on off LED BO 188 Error Board 6 Device General General func tions OUT on off LED BO 189 Err...

Page 201: ...A 9 Group Alarms 187 6MD665 Manual C53000 G1876 C103 3 A 9 Group Alarms No Description No Description ...

Page 202: ...P1 Voltage Input U MU1P_1 Mea sured Value Processing 1P1 Current Input I MU1P_1 Mea sured Value Processing 1P1 Voltage U MU1P_1 Mea sured Value Processing 106 146 no 3 2 CFC CD DD 134 152 no 9 1 1P1 Current I MU1P_1 Mea sured Value Processing 106 146 no 3 1 CFC CD DD 134 152 no 9 2 1P1 Active Power P MU1P_1 Mea sured Value Processing 106 146 no 3 3 CFC CD DD 134 152 no 9 3 1P1 Reactive Power Q MU1...

Page 203: ...P_3 134 154 no 9 4 CFC CD DD 1P3 Apparent Power S MU1P_3 134 154 no 9 5 CFC CD DD 1P3 Phase Angle Phi MU1P_3 134 154 no 9 6 CFC CD DD 1P3 Active Power Factor Cosine Phi MU1P_3 134 154 no 9 7 CFC CD DD 1P3 Reactive Power Factor Sine Phi MU1P_3 134 154 no 9 8 CFC CD DD 1P3 Frequency of U MU1P_3 134 154 no 9 9 CFC CD DD 3P1 Voltage Input U1 MU3P_1 Mea sured Value Processing 3P1 Voltage Input U2 MU3P_...

Page 204: ...ing 106 148 no 9 3 CFC CD DD 134 151 no 9 11 3P1 Active Power Three Phase MU3P_1 Mea sured Value Processing 106 148 no 9 7 CFC CD DD 134 151 no 9 12 3P1 Reactive Power Three Phase MU3P_1 Mea sured Value Processing 106 148 no 9 8 CFC CD DD 134 151 no 9 13 3P1 Apparent Power Three Phase MU3P_1 Mea sured Value Processing 134 151 no 9 14 CFC CD DD 3P1 Phase Angle Three Phase MU3P_1 Mea sured Value Pro...

Page 205: ...s ing 134 155 no 9 6 CFC CD DD A1 Apparent Power S MUAron_1 Measured Value Process ing 134 155 no 9 7 CFC CD DD A1 Phase Angle Phi MUAron_1 Measured Value Process ing 134 155 no 9 8 CFC CD DD A1 Active Power Factor Cosine Phi MUAron_1 Measured Value Process ing 134 155 no 9 9 CFC CD DD A1 Reactive Power Factor Sine Phi MUAron_1 Measured Value Process ing 134 155 no 9 10 CFC CD DD A1 Frequency MUAr...

Page 206: ... 9 3 CFC CD DD Sync voltage difference U1 U2 SYNC function 2 130 2 no 9 2 CFC CD DD Sync angle between U1 U2 SYNC function 2 130 2 no 9 6 CFC CD DD Sync frequency f1 SYNC function 2 130 2 no 9 4 CFC CD DD Sync frequency f2 SYNC function 2 130 2 no 9 7 CFC CD DD Sync frequency difference f1 f2 SYNC function 2 130 2 no 9 5 CFC CD DD Sync3 Voltage input U1 SYNC function 3 Sync3 Voltage input U2 SYNC ...

Page 207: ...CFC CD DD Sync angle between U1 U2 SYNC function 5 130 5 no 9 6 CFC CD DD Sync frequency f1 SYNC function 5 130 5 no 9 4 CFC CD DD Sync frequency f2 SYNC function 5 130 5 no 9 7 CFC CD DD Sync frequency difference f1 f2 SYNC function 5 130 5 no 9 5 CFC CD DD Sync6 Voltage input U1 1 PE SYNC function 6 Sync6 Voltage input U1 2 PE SYNC function 6 Sync6 Voltage input U2 SYNC function 6 Sync voltage U...

Page 208: ...ge input U1 2 PE SYNC function 8 Sync8 Voltage input U2 SYNC function 8 Sync voltage U1 SYNC function 8 130 8 no 9 1 CFC CD DD Sync voltage U2 SYNC function 8 130 8 no 9 3 CFC CD DD Sync voltage difference U1 U2 SYNC function 8 130 8 no 9 2 CFC CD DD Sync angle between U1 U2 SYNC function 8 130 8 no 9 6 CFC CD DD Sync frequency f1 SYNC function 8 130 8 no 9 4 CFC CD DD Sync frequency f2 SYNC funct...

Page 209: ... Start UP E50417 G1176 C152 A2 3 DIGSI CFC Manual E50417 H1176 C098 A4 4 SIPROTEC SIGRA 4 Manual E50417 H1176 C070 A2 5 PROFIBUS DP Communication profile available on DIGSI CD and on the Inter net C53000 L1840 B001 03 6 PROFIBUS DP Bus mapping 6MD663 6MD664 available on DIGSI CD and on the Internet C53000 L1840 B011 03 ...

Page 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...

Page 211: ...tion Bit pattern indication is a processing function by means of which items of digital process information applying across several inputs can be detected together in paral lel and processed further The bit pattern length can be specified as 1 2 3 or 4 bytes BP_xx Bit pattern indication Bitstring Of x Bit x designates the length in bits 8 16 24 or 32 bits CFC Continuous Function Chart CFC is a gra...

Page 212: ...ction is the total of all the means and measures used to protect electrostatic sensitive devices Single command Single commands are process outputs which indicate 2 process states for example ON OFF at one output Single point indica tion Single indications are items of process information which indicate 2 process states for example ON OFF at one output Electromagnetic compatibility Electromagnetic...

Page 213: ...ttent input for example due to a relay contact fault is switched off after a configurable monitoring time and can thus not generate any further signal changes The function prevents overloading of the system when a fault arises FMS communica tion branch Within an FMS communication branch the users communicate on the basis of the PROFIBUS FMS protocol via a PROFIBUS FMS network General interroga tio...

Page 214: ...rmediate position 00 Double point indication IS Internal single point indication Single point indication IS_F Single point indication fleeting Transient information Single point indication IEC International Electrotechnical Commission IEC Address Within an IEC bus a unique IEC address has to be assigned to each SIPROTEC 4 device A total of 254 IEC addresses are available for each IEC bus IEC commu...

Page 215: ...oject window displays the names and icons of objects which represent the contents of a container selected in the tree view Because they are dis played in the form of a list this area is called the list view Master Masters may send data to other users and request data from other users DIGSI oper ates as a master MLFB Number MLFB is the abbreviation for MaschinenLesbare FabrikateBezeichnung machine ...

Page 216: ... the set of all parameters that can be set for a SIPROTEC 4 device PROFIBUS PROcess FIeld BUS the German process and field bus standard as specified in the standard EN 50170 Volume 2 PROFIBUS It defines the functional electrical and mechanical properties for a bit serial field bus PROFIBUS Address Within a PROFIBUS network a unique PROFIBUS address has to be assigned to each SIPROTEC 4 device A to...

Page 217: ...real SIPROTEC 4 device with all the setting values and process data it contains SIPROTEC 4 variant This object type represents a variant of an object of type SIPROTEC 4 device The device data of this variant may well differ from the device data of the source object However all variants derived from the source object have the same VD address as the source object For this reason they always correspo...

Page 218: ...SI Manager must be transferred to the SIPROTEC 4 device in order to allow communication with DIGSI Device Editor Combination matrix Up to 16 compatible SIPROTEC 4 devices can communicate with one another in an Inter Relay Communication combination IRC combination Which device exchanges which information is defined with the help of the combination matrix VFD A VFD Virtual Field Device includes all ...

Page 219: ...s 3 128 D DC voltage 129 De interlockings 27 Dead Bus 61 Dead bus connection 52 Dead Line 61 Dead line connection 52 Declaration of Conformity i Dimensions Cabinet mounting 148 Dimensions D subminiature connector Dongle cable 151 Dimensions Detached operator panel 150 Dimensions Panel flush mounting 148 Dimensions Surface mounted housing with detached operator panel 149 Dimensions Surface mounted ...

Page 220: ...edback information 28 Mounting with Detached Operator Panel 109 Mounting without operator panel 110 O Operating measured values 30 144 Operating metered values 43 Operator Interface 130 Ordering information 154 Output relays binary outputs 130 P Password 10 Power metering 43 Power supply 129 PROFIBUS 97 Pulse metered value 43 Q Qualified Personnel ii R Rated system frequency 11 Rated transformer c...

Page 221: ...ode 13 118 Test System Interface 119 Threshold switch 49 49 Threshold value 61 Time Stamping 147 Time synchronisation 8 Time Synchronization Interface 113 133 Transmission Block 118 Transmission thresholds 49 U Upper voltage limit Vmax 61 User Definable Functions 141 V Vibration and Shock Stress During Operation 135 Vibration and Shock Stress During Transport 135 Voltage application 52 53 Voltage ...

Page 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...

Reviews: