3 Installation and Commissioning
114
6MD665 Manual
C53000-G1876-C103-3
Table 3-7
D-subminiature connector assignment of the time synchronization interface
1)
assigned, but not used
3.2.7
Optical Fibers
WARNING!
Warning of Laser rays!
Non–observance of the following measure can result in death, personal injury or sub-
stantial property damage.
Do not look directly into the fibre-optic elements!
Signals transmitted via optical fibers are unaffected by interference. The fibers guar-
antee electrical isolation between the connections. Transmit and receive connections
are shown with the symbols for transmit and for receive.
The normal setting of the character idle state for the fibre optic cable interface is "Light
off". If the character idle state is to be changed, use the operating program DIGSI
®
, as
described in the SIPROTEC
®
system description /1/.
3.2.8
Checking Power System Connections
Before the device is energized for the first time, the device should be in the final oper-
ating environment for at least 2 hours to equalize the temperature, to minimize humid-
ity and avoid condensation. Connections are checked with the device at its final loca-
tion. The plant must first be switched off and grounded.
Pin No.
Designation
Signal Meaning
1
P24_TSIG
Input 24 V
2
P5_TSIG
Input 5 V
3
M_TSIG
Return Line
4
–
5
Shield
Shield Potential
6
–
–
7
P12_TSIG
Input 12 V
8
P_TSYNC
Input 24 V
9
SHIELD
Shield Potential
Summary of Contents for SIPROTEC 6MD665
Page 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Page 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Page 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Page 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...