2 Functions
70
6MD665 Manual
C53000-G1876-C103-3
Note
Due to the cyclical method of operation of the IRC, only indications whose value
changes are pending longer than 20 ms are transferred.
Electrical RS485
connection
Figure 2-26
Connection of bay controllers to inter relay communication (electrical)
The connection between the devices occurs electrically via an RS485 interface. The
electrical connections are terminated with resistors at the ends (first and last device),
which are set via jumpers in the 6MD665 device. The jumper settings can be found
in Chapter Installation and Commissioning.
One of the following operating modes can be selected in DIGSI
®
using the serial inter-
face settings.
Table 2-14
Operating mode of the IRC interface (electrical)
Transmission mode
Baud rate
HDLC
125 KBaud, 250 KBaud, 1 MBaud, 1.25 MBaud
UART
115 KBaud or 250 KBaud