2.5 Metered Value Processing
43
6MD665 Manual
C53000-G1876-C103-3
2.5
Metered Value Processing
The device can add up couner pulses of an external counter recorded via a binary
input. Additionally, the bay control unit can calculate energy values from measured
values.
2.5.1
Description
Operation of pulse
metered value
The Bay Processing Unit 6MD665 forms the metered value as a sum of the externally
generated counter pulses of a power meter. The pulses are read in via a binary input.
The metered value receives a unit based on the following table. It has the same pre-
cision as the external counter and can also be an adjusted metered value.
Operation of
metered values cal-
culated from mea-
sured values
With the metered values calculated from measured values , the Bay Processing Unit
6MD665 forms the power from the applied current and voltage values or from any
desired measured values and integrates this calculated power value over time. The
result is an energy value with the precision of the device (0.5 %), i.e. an operating
metered value which cannot be used for adjustment.
Table 2-4
Operating metered values
The following types of information can be allocated to a metered value window in the
DIGSI
®
allocation matrix.
• Metered values calculated from measured values
• Pulse metered value
The same operations are possible with pulse and metered values calculated from
measured values, e.g. reset - to set back to a specified value etc..
Using the pulse metered value
In this example, the active power of a 3-phase system is to be integrated over time and
displayed as a metered value. The pulse output of an external device which supplies
the active power pulse accordingly, is to be applied to a binary input of the device. The
power corresponding to a pulse must be known.
Inserting a pulse
metered value
Open the allocation matrix of the device and select Only measured and metered
values as the information type.
Create the group Energy in the allocation matrix.
Open the information catalog and select the line PowerMeter (MVMV) under Power-
Meter
→
PowerMeter.
Measured values
Possible units
W
p
+
Real power, output
kWh, MWh, GWh
W
p
–
Real power, input
kWh, MWh, GWh
W
q
+
Reactive power, output
kVARh, MVARh, GVARh
W
q
–
Reactive power, input
kVARh, MVARh, GVARh
Summary of Contents for SIPROTEC 6MD665
Page 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Page 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Page 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Page 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...