4 Technical Data
140
6MD665 Manual
C53000-G1876-C103-3
Synchronisation function delay after start
250 ms
Maximum wait time (max. synchronisation
duration
0.01 s to 600.00 s (0.01 s increments)
Tolerance of all times
1 % of setting value or 10 ms
Operating range
Synchrocheck at rated frequency
50 Hz
±
2 Hz
60 Hz
±
2 Hz