3.1 Installation and Connections
103
6MD665 Manual
C53000-G1876-C103-3
I/O-5 module
Check the set rated currents of the current input transformers here. All jumpers must be set for
one rated current, i.e. respectively one jumper (X61 to X63) for each input transformer and addi-
tionally the common jumper X60.
Figure 3-4
I/O-5 input/output module with representation of the jumpers required for checking the settings
Jumpers X71, X72 and X73 on the I/O–5 input/output module serve for setting the bus
address. Their position may not be changed. The table shows the factory setting of the
jumpers. The insertion slot of the module is described in Section Module arrange-
ment.