12 Applied Standards and Approvals
SINAUT MD741-1
C79000-G8976-C236-05
133
Directive 94/9/EC (ATEX)
Additional marking (sample)
6NH9741-1AA00, SINAUT MD741-1 GSM/GPRS Router
Applied standards
●
EN60079-15 (Type of protection “n”)
Classification
Group II, Category 3, Gas Atmosphere, Non-sparking equipment, Temperature
class T4, Ambient temperature range: -20°C … +60°C
Specific Conditions of Use:
1. The SINAUT MD741-1 shall be installed in an Enclosure which maintains an
ingress protection rating of IP54; meets the enclosure requirements of
EN60079-0 and is only accessible with the use of a tool.
2. The USB (X1) port shall not be used.
3. On installation the SINAUT MD741-1 shall be provided with supply transient
protection external to the apparatus such that the voltage at the supply
terminals of the SINAUT MD741-1 shall not exceed 42 V.
4. When the Antenna is mounted external to the final Enclosure it shall be
mounted and connected in a manner which maintains an ingress protection
rating of IP54 and meets the enclosure requirements of EN60079-0.