Technical Data
SINAUT MD720-3
72
C79000-G8976-C211
Supply current / no
connection or
connection to
SINAUT MICRO
SC without data
exchange
In 90mA at 12V
In 50mA at 24V
In 40mA at 30V
Temperature range Operation: –20°C up to +60°C
Storage: –25°C up to +85°C
Ambient
conditions
Humidity
0-95 %, not condensing
Construction
Top-hat rail housing
Material
Synthetic material
Protection category IP40
Dimensions
114 mm x 22,5 mm x 99 mm (L x W x H)
Mechanics
Weight
Approx. 150g
CE
Yes
R&TTE
Yes
EMV / ESD
EN 55024, EN 55022 Class A, EN 61000-6-2
ATEX
III 3 G EEx nA II T4 Ta=-20°C-60°C
KEMA 03 ATEX 1229 X
FM
CLI, DIV2, GP. A,B,C,D T4 Ta=-20°C-60°C
CLI, Zone 2 IIC, T4 Ta=-20°C-60°C
Approvals
UL E301826
Interface X1
Signals
(Signal direction DTE)
SUB-D9 socket, Pin assignment
RS232
Pin1 DCD Output
Pin2 RXD Output
Pin3 TXD Input
Pin4 DTR Input
Pin5 GND Signal
ground
Pin6 DSR Output
Pin7 RTS Input
Pin8 CTS Output
Pin9 RI Output