Service functions
SINAUT MD720-3
C79000-G8976-C211
69
Upload a new firmware into the SINAUT MD720-3
When the service connection is established, you can start to upload the new
firmware.
1. With Notepad (belongs to Windows) create a file with the name
!cmdfile
. The
file name must not have any extension (e.g.: .txt). The first line in this file is:
STORE FirmwareName.BIN
Instead of „FirmewareName.BIN“ write the name of the new firmware file.
2. At the Ftp>-prompt enter:
put
FirmwareName.BIN
Press Enter. Instead of „FirmewareName.BIN“ write the name of the new
firmware file.
3. Then at the Ftp>-prompt enter:
put !cmdfile
Press Enter.
After the firmware file and the !cmdfile file are successfully uploaded the
SINAUT MD720-3 will start to install the new firmware. This process can last
up to 10 minutes. After this the SINAUT MD720-3 restarts. Then the SINAUT
MD720-3 is ready again.
The firmware update is ready, if:
•
the LED “Q” is ON and the LED “C” blinks (MD720-3 with SIM card)
or
•
the LED “S” blinks and the LED “C” is ON (MD720-3 without SIM card).
Release the local service connection
Release the local service connection, if you do not need it anymore.
1. At the Ftp>-prompt enter:
quit
Then press Enter.
2. Then also tear-down the network connection to the device. To do so right-click
the icon in the Windows task bar.
Summary of Contents for SINAUT MD720-3
Page 10: ...Contents SINAUT MD720 3 10 C79000 G8976 C211 ...
Page 22: ...Connecting the device and switching on the device SINAUT MD720 3 22 C79000 G8976 C211 ...
Page 45: ...SINAUT MD720 3 in Terminal Mode SINAUT MD720 3 C79000 G8976 C211 45 ...
Page 74: ...Technical Data SINAUT MD720 3 74 C79000 G8976 C211 ...
Page 76: ...Technical Data SINAUT MD720 3 76 C79000 G8976 C211 ...