List of signals for the analog outputs
Signal
Parameter
Unit
Scaling
(100% = ...)
Speed setpoint for setpoint filter
r0060
1/min
p2000
Motor speed unsmoothed
r0061
1/min
p2000
Actual speed smoothed
r0063
1/min
p2000
Output frequency
r0066
Hz
Reference fre‐
quency
Output current
r0068
Aeff
p2002
DC-link voltage
r0070
V
p2001
Torque setpoint
r0079
Nm
p2003
Output power
r0082
kW
r2004
For diagnostic purposes
Control deviation
r0064
1/min
p2000
Slip frequency
r0065
Hz
Reference fre‐
quency
Phase current actual value
r0069
A
p2002
Control factor
r0074
%
Reference control
factor
Field-generating current setpoint
r0075
A
p2002
Field-generating actual current
r0076
A
p2002
Torque-generating current setpoint
r0077
A
p2002
Torque-generating actual current
r0078
A
p2002
Flux setpoint
r0083
%
Reference flux
Actual flux
r0084
%
Reference flux
DC-link voltage
r0088
V
p2001
Phase voltage
r0089
V
p2001
For further diagnostic purposes
Speed controller output
r1480
Nm
p2003
I component of speed controller
r1482
Nm
p2003
Scaling
Variable
Scaling parameter
Default for quick commissioning
Reference speed
100% = p2000
p2000 = Maximum speed (p1082)
Reference voltage
100% = p2001
p2001 = 1000 V
Reference current
100% = p2002
p2002 = Current limit (p0640)
Reference torque
100% = p2003
p2003 = 2 x rated motor torque
Reference power
100% = r2004
r2004 = (p2003 x p2000 x pi) / 30
Reference frequency
100 % = r2000 / 60
Reference control factor 100% = Maximum output voltage
without overload
Reference flux
100% = Rated motor flux
Reference temperature
100% = 100° C