Function diagrams
● 1590
● 1690
● 5060
● 6300
Note
A simple rise in voltage can be achieved with parameter p6890. Refer to function diagram
6300.
8.5.2
Analog and digital inputs/outputs
8.5.2.1
Analog outputs
The customer terminal block is equipped with two analog outputs for outputting setpoints via
current or voltage signals.
Factory setting:
● AO0: Actual speed value 0
● AO1: Actual motor current value 0
Adjustable parameters
● p4071 Analog outputs, signal source
● p4073 Analog outputs, smoothing time constant
● r4074 Analog outputs, actual output voltage/current
● p4076 Analog outputs, type
● p4077 Analog outputs, characteristic value x1
● p4078 Analog outputs, characteristic value y1
● p4079 Analog outputs, characteristic value x2
● p4080 Analog outputs, characteristic value y2
Function diagrams
● 1840
● 9572