Adjusting the -K110 and -K120 delay times
A
Safety relay -K110 ...
①
Off-delay time
B
Time relay -K120
②
Runtime setting in %
③
Time range setting
④
Time range display
⑤
Display function
⑥
Function selection
Figure 3-13
Safety relay -K110 and time relay -K120
The delay times set at the factory can be changed by the customer using the closed-loop
controllers. Change the settings of the time relay -K120 only when it is disconnected from the
power supply.
When you plan your settings, you must comply with the following rules:
T
delay K110
> (T
delay- K120
+ T
tolerance
*)
*T
tolerance
= 1 second
If this rule is not observed, safety is not restricted in any way. However, the second switch-off
signal path via the circuit-breaker is used for each activation.