SIMOTION D410-2
Manual, 02/2012
33
Interfaces
3
3.1
Overview of interfaces
This chapter describes the SIMOTION D410-2 DP interfaces. The arrangement of the
interfaces on the module can be found in the SIMOTION D410-2 DP representation
(Page 18) chapter.
Available interfaces
Table 3- 1
Overview of the available SIMOTION D410-2 DP interfaces
Interface
Type
Connector type
X100
DRIVE-CLiQ interface (DQ)
8-pin RJ45plus socket to connect DRIVE-
CLiQ nodes
X21
PROFIBUS DP/MPI interface
9-pin SUB-D socket to connect to
PROFIBUS DP or MPI
X24
PROFIBUS DP interface
9-pin SUB-D socket to connect to
PROFIBUS DP
X23
Encoder interface (ENC)
15-pin SUB-D socket for connecting HTL,
TTL and SSI encoders.
X120
Temperature sensor connection, fail-
safe digital inputs
12-pin spring-loaded terminal
X121
Isolated digital inputs, fast digital I/Os 12-pin spring-loaded terminal
X130
Isolated digital input, fail-safe digital
output
8-pin spring-loaded terminal
X131
Fast digital I/Os, analog input
8-pin spring-loaded terminal
X124
Power supply connection
4-pin screw-type terminal connection
X127 P1
Ethernet interface (PN/IE)
8-pin RJ45plus socket for Ethernet
connection (LAN)
T0, T1, T2
and G
Measuring sockets
Sockets to output analog signals
PM-IF
Power Module Interface
8-pin direct connector to connect to a
blocksize power module
Non-usable interfaces
Table 3- 2
Overview of the unavailable SIMOTION D410-2 DP interfaces
Interface
Designation
Connector type
Interface for BOP
BOP
8-pin multipoint connector