Electrical connection
Standard motors
56100000002001, 02/2013
47
6.2
Tightening torques
6.2.1
Cable glands
Note
Take care not to damage the cable jacket.
Tightening torques must be adapted to suit the type of cable jacket material in use.
You should refer to the table in order to find the correct tightening torque for any
metal and plastic cable glands that are to be mounted directly on the machine, as
well as for any other screw-type connections (such as adapters).
Table 6-1 Tightening torques for cable glands
Clamping range in mm
Metal
± 10%
Nm
Plastic
± 10%
Nm
Standard
-30 °C ... 100 °C
Ex
-30 °C ... 90 °C
Ex
-60 °C ... 105 °C
O ring
Cord ∅
mm
M 12 x 1,5
8
1,5
3,0 ... 7,0
-
M 16 x 1,5
10
2
4,5 ... 10,0
6,0 ... 10,0
M 20 x 1,5
7,0 ... 13,0
6,0 ... 12,0
M 25 x 1,5
12
4
9,0 ... 17,0
10,0 ... 16,0
M 32 x 1,5
11,0 ... 21,0
13,0 ... 20,0
M 40 x 1,5
18
19,0 ... 28,0
20,0 ... 26,0
M 50 x 1,5
26,0 ... 35,0
25,0 ... 31,0
M 63 x 1,5
20
6
34,0 ... 45,0
-
2
6.2.2
Terminal boxes, end shields, grounding conductors,
sheet metal fan covers
Note
The specified tightening torques are applicable unless other values are indicated.
Summary of Contents for SIMOTICS 1LA
Page 36: ......
Page 85: ...49 ...
Page 88: ...COD 1261 R3 INDUSTRY PROCESS AND AUTOMATION SOLUTIONS w w w b o n f i g l i o l i c o m ...
Page 89: ... i Bonfiglioli Trasmital 300 series Installation use and service manual ATEX INCLUDED ...
Page 130: ... Bonfiglioli Trasmitol 41 ...
Page 132: ......
Page 135: ...SPRING APPLIED BRAKE WITH ELECTROMAGNETIC RELEASE 38 mm Page 2 of 2 180 Volts 16 39599 ...