5. Select the check boxes for the devices whose device descriptions are to be integrated. On
the devices that are not yet integrated or have been integrated with an older version, the
check box is automatically selected.
The "Fieldbus Foundation" directory contains all FF devices (device library of the Fieldbus
Foundation and other individual devices).
You can work with a split device list window.
Note
Integrating device descriptions
Many FF devices require information that is stored in other device descriptions.
Recommendation:
Integrate all device descriptions that provided with the SIMATIC PDM "Device Library" DVD.
6. Select the Catalog > Integration... menu command.
The device descriptions are transferred to the PC.
Note
During the device description integration
Do not open any SIMATIC programs until the device description integration has completed.
Additional information
Online help for SIMATIC PDM
5.2
Configuring
5.2.1
How to prepare a FOUNDATION Fieldbus for FF devices
An example of a plant configuration can be found in section "Introduction (Page 7)".
Recommendation for using symbolic names
Assign symbolic names to the signals of the FF devices. Symbolic names facilitate the
configuration and documentation of the automation task. The use of symbolic names is
considered below.
Requirements
● SIMATIC PCS 7 is installed.
● SIMATIC PDM is installed with the add-on package "SIMATIC PDM Communication
FOUNDATION Fieldbus" (standard for PCS 7).
Engineering
5.2 Configuring
FOUNDATION Fieldbus
Commissioning Manual, 02/2015, A5E32711026-AC