A.6
Basics for PROFINET
A.6.1
Pin assignment of the RJ45 connection plug
Table A-10
Pin assignment of the RJ45 connector
View RJ45‑plug socket
Contact
assignment
6KLHOG
1
RD (Receive Data +)
2
RD_N (Receive Data –)
3
TD (Transmit Data +)
4
Ground
5
Ground
6
TD_N (Transmit Data –)
7
Ground
8
Ground
A.7
CFU PA: Basics for PROFIBUS PA
A.7.1
PROFIBUS addresses of the PROFIBUS PA field devices on the CFU PA (FBn)
You can connect all field devices that are suitable for PROFIBUS PA to the CFU PA.
The PROFIBUS addresses are permanently assigned to the fieldbus connections FB<n>.
Fieldbus connection
PROFIBUS PA address
FB0
20
FB1
21
FB2
22
FB3
23
FB4
24
FB5
25
FB6
26
FB7
27
Appendix
A.7 CFU PA: Basics for PROFIBUS PA
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
189
Summary of Contents for Simatic CFU