A.9.2.4
CFU DIQ: Address space of the submodule DIQ16 DC24V/0.5A, Counter
Abbreviations
● "IB" stands for input byte, that is, the submodule start address in the input area
● "QB" stands for output byte, that is, the submodule start address in the output area
● "DI" stands for digital input
● "DQ" stands for digital output
● "-" stands for reserved (unused)
Address space
The following tables show the allocation of the CFU DIQ address space with the digital inputs
Channel 0 and Channel 1 as counters without evaluation of the status.
Input area
The table shows the allocation of the address space of the feedback interface.
Table A-17
Address space of the CFU DIQ with submodule "DIQ16 DC24V/0.5A, Counter"
IB x +
7
6
5
4
3
2
1
0
0
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
1
DI15
DI14
DI13
DI12
DI11
DI1
0
DI9
DI8
2
Count value 0 / Frequency value 0
3
4
5
6
LD_ER‐
ROR_0
LD_STS_SLO
T_0
STS_M_INTER‐
VAL_0
STS_SW_GAT
E_0
-
-
STS_GATE
_0
STS_DQ_0
7
Count value 1 / Frequency value 1
8
9
10
11
LD_ER‐
ROR_1
LD_STS_SLO
T_1
STS_M_INTER‐
VAL_1
STS_SW_GAT
E_1
-
-
STS_GATE
_1
STS_DQ_1
IB 6 / IB 11
Action
Meaning
1xxx xxx
LD_ERROR_<x> Error in the control byte or load value is greater than high counting limit
x1xx xxx
LD_STS_SLOT_<
x>
A status change of LD_STS_SLOT_<x> shows that a valid load request (LD_SLOT)
has been detected and executed.
Appendix
A.9 Drivers, parameters, diagnostic messages and address space
SIMATIC CFU
198
Commissioning Manual, 08/2019, A5E39252870-AD
Summary of Contents for Simatic CFU
Page 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...