LED displays on the BusAdapter
Table 9-3
Status display "LK1" and "LK2" on the BusAdapter
LEDs "LK1" and
"LK2"
Meaning
Solution
ON
There is an Ethernet connection between the PRO‐
FINET IO interface of the CFU and a communication
partner (for example IO controller).
-
Off
There is no Ethernet connection between the PRO‐
FINET IO interface of the CFU and a communication
partner (for example IO controller).
Check whether the bus cable to the switch/IO
controller is interrupted.
LED display on channel (DIQ<n>)
Table 9-4
Area: DIQ
ER/MT (error/main‐
tenance)
DIQ<n> - LED
Maintenance
Message
Off
On
Good status (signal
on)
-
Off
Off
Good status (signal
off)
-
Flashes
Flashes
Interrupt
● Wire break
● Short-circuit to L+
● Short-circuit to M
● Actuator shutdown detected
Flashes
*
Interrupt
● Temperature rise
● Missing load voltage
● External power supply detected
● CFU DIQ: Communication error
CFU PA only: LED display on fieldbus connection (FB<n>)
Table 9-5
Area: Fieldbus
ER/MT (error/main‐
tenance)
FB<n> - LED
Maintenance
Message
Off
On
Good status: Device
connected and
ready for operation
Off
Off
Good status: No de‐
vice connected and
configured
Off
Flashes
-
Startup phase of the field device
Diagnostics of the CFU
9.2 Diagnostics via LED displays
SIMATIC CFU
110
Commissioning Manual, 08/2019, A5E39252870-AD
Summary of Contents for Simatic CFU
Page 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...