8.9.4
CFU PA: Parameter assignment of PROFIBUS PA field device (online)
Status of the field devices
You can determine the status of the field devices in the "CFU ... Configuration; Commissioning
Wizard" dialog of SIMATIC PDM. You can find information on this in section "CFU: Configuring
Requirement
A profile is assigned to the field device in HW Config.
The configuration of the CFU PA using the Commissioning Wizard of SIMATIC PDM takes
effect if the "Change configuration" check box is selected in step 5/6 of the Commissioning
Wizard (check box is not selected by default).
Note
"Change configuration" check box
The configuration in HW Config and the selection of the "Selected IO" in the Commissioning
Wizard are performed independent of each other.
Both configurations must match. Otherwise, a diagnostic interrupt is output.
If, at any point in time, the configuration in HW Config and the configuration of the "Selected IO"
in the "CFU ... Configuration; Commissioning Wizard" of the SIMATIC PDM are the same for all
field devices, the "Change configuration" check box is automatically reset.
Procedure
1. Select the CFU PA in HW Config.
2. Double-click the field device in the slot list.
SIMATIC PDM opens.
3. Assign the field device parameters using SIMATIC PDM.
Dependency of configuration of the CFU PA
● The field device is not configured on the CFU PA.
The CFU PA automatically sets the lowest PA profile available for the IO in the field device.
You can change the selection at any time. You can find additional information on this in
section "Using a wizard for CFU configuration (Page 72)".
● The field device is configured using the Commissioning Wizard.
The "Selected IO" is selected (for example: a "Transmitter 2 AI" is selected for FB 2).
Commissioning
8.9 CFU PA: Commissioning (online)
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
103
Summary of Contents for Simatic CFU
Page 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...