10.3
Export/import device description
10.3.1
EDD: Exporting parameters
You can use this function to export the parameters set in a CFU to an EDD (data backup).
The functionality is available as of firmware V1.2 (EDD 3.x).
Procedure
1. Open the parameter assignment of the CFU in SIMATIC PDM via the hardware
configuration.
2. Execute the read back of the configuration for the CFU in SIMATIC PDM: "Upload to PG/
PC...".
3. Select the check box "Import/Export Mode".
4. Export the data of the CFU.
5. Clear the check box "Import/Export Mode".
10.3.2
EDD: Importing parameters
With this function you overwrite the set device parameters with exported data.
Application:
● Restoring the parameters of the CFU
● Applying the parameters of a different CFU
The functionality is available as of firmware V1.2 (EDD 3.x).
Requirement
The exported CFU data are available.
Procedure
1. Open the parameter assignment of the CFU in SIMATIC PDM via the hardware
configuration.
2. Select the check box "Import/Export Mode".
3. Import the data of the CFU.
4. Clear the check box "Import/Export Mode".
Servicing and maintenance
10.3 Export/import device description
SIMATIC CFU
116
Commissioning Manual, 08/2019, A5E39252870-AD
Summary of Contents for Simatic CFU
Page 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...