Additional information
● You can find information about the power supply in section "Connecting the power supply
● You can find information about the ambient temperature in section "Mechanical and climatic
ambient conditions for operation (Page 160)".
● System manual Principles of Explosion Protection (
support.industry.siemens.com/cs/ww/en/view/12521844
); section
"Installation in
hazardous areas"
11.3.2.4
Installing SIMATIC CFU with aluminum housing on the mounting surface
Requirement
● The mounting surface must be level, stable and free from vibrations.
● Select the mounting material that best suits the mounting surface.
Tools required
● 4 fixing screws M6; dowels depending on the mounting surface
● Screwdriver suitable for the screws used
● For housing screws: Screwdriver PH2 or with 9 mm blade width
Installing the housing
Note
Note on installation direction
Refer to section "Installation instructions (Page 133)".
Compact Field Unit in the housing for use in a hazardous area
11.3 Configuration with SIMATIC CFU with aluminum housing
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
137
Summary of Contents for Simatic CFU
Page 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...