5
5-3
C7-626 / C7-626 DP Control Systems
C79000-G7076-C626-01
Specific Data of the Digital Input Function
Number of inputs
16
Cable length
S
Unshielded
600 m
Voltages, Currents, Potentials
Nominal load voltage L +
24 VDC
Number of simultaneously
energizable inputs
16
Galvanic isolation
S
In groups of
Yes (optocoupler)
16
Permissible potential
difference
S
Between the M terminals
of the groups
S
Insulation resistance
–
500 VDC
Status, Interrupts, Diagnostics
Interrupts
No
Diagnostic functions
No
Data for Selecting a Sensor
Input voltage
S
Nominal voltage
S
For “1” signal
S
For “0” signal
24 VDC
from 11 to 30 V
from -3 to 5 V
Input current
S
For “1” signal
from 6 to 11.5 mA
Input delay time
S
Programmable
S
At “0” to “1”
S
At “1” to “0”
No
from 1.2 to 4.8 ms
from 1.2 to 4.8 ms
Input characteristic
In accordance with
DIN EN 61131-2
(IEC 1131, Part 2)
Type of input in accordance
with IEC 1131
Type 2
Connection of 2-wire BEROs
S
Permissible quiescent
current
Possible
2 mA
C7 Digital Input/Output
Summary of Contents for SIMATIC C7-626
Page 18: ...1 1 6 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Product Overview ...
Page 122: ...A A 8 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 General Technical Specifications ...
Page 138: ...Glossary 10 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Glossary ...
Page 142: ...Index 4 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Index ...