6
6-17
C7-626 / C7-626 DP Control Systems
C79000-G7076-C626-01
Block diagram
DAC
AO1
Galvanic
isolation
Figure 6-12
Block Diagram of the Analog Output Function
Technical Specifications
Specific Data of the Analog Output
Number of outputs
1
Cable length, shielded
200 m
Voltages, Currents, Potentials
Galvanic isolation
Yes
Insulation resistance
500 VDC
Measurement ranges:
Voltage
Current
V/A at different pins –>
no coding pin
10 V
20 mA, 4...20 mA
Analog Value Generation
Resolution (including
overrange)
S
10 V;
20 mA;
4 to 20 mA
12 bits incl. sign
Conversion time
max. 0.8 ms
Settling time
S
For resistive load
S
For capacitive load
S
For inductive load
0.1 ms
3.3 ms
0.5 ms
Substitute value injectable
Yes, can be assigned
parameters
Interference Suppression, Error Limits
Measuring tolerance
1% of end value
Basic error limit (operational
limit at 25
_
C, referred to
output range)
S
Voltage
S
Current
1%
1%
Output ripple (referred to
output range)
0.05 %
Status, Interrupts, Diagnostics
Interrupts
S
Diagnostic interrupt
Yes, can be assigned
parameters
Diagnostic functions
S
Diagnostic information can
be read
Yes, can be assigned
parameters
Yes, group error/fault
C7 Analog Input/Output
Summary of Contents for SIMATIC C7-626
Page 18: ...1 1 6 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Product Overview ...
Page 122: ...A A 8 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 General Technical Specifications ...
Page 138: ...Glossary 10 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Glossary ...
Page 142: ...Index 4 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Index ...