5
5-6
C7-626 / C7-626 DP Control Systems
C79000-G7076-C626-01
Specific Data of the Digital Output Function
Number of outputs
16
Cable length
S
Unshielded
600 m
Voltages, Currents, Potentials
Nominal load voltage L +
24 VDC / 0.5 A
Total current of the outputs
(per group)
2 A
Galvanic isolation
S
In groups of
Yes (optocoupler)
8
Insulation resistance
500 VDC
Status, Interrupts, Diagnostics
Interrupts
No
Diagnostic functions
No
Data for Selecting an Actuator
Output voltage
S
At “1” signal
L + (– 0.8 V)
Output current
S
At “1” signal
nominal value
Permissible range
S
At “0” signal (quiescent
current)
0.5 A
5 mA..0.5 mA
max. 0.5 mA
Lamp load
max. 5 W
Parallel switching of 2 outputs
S
For logic operations
S
For enhancing
performance
Possible (outputs of
the same group only)
Not possible
Activating a digital input
Yes
Max. switching frequency
S
With resistive load/lamp
load
S
With inductive load
100 Hz
0.5 Hz
Inductive cutoff voltage
limited (internally) to
L + (– 48 V)
Short-circuit protection of the
outputs
S
Operating point
Yes, electronically
timed
1 A
C7 Digital Input/Output
Summary of Contents for SIMATIC C7-626
Page 18: ...1 1 6 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Product Overview ...
Page 122: ...A A 8 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 General Technical Specifications ...
Page 138: ...Glossary 10 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Glossary ...
Page 142: ...Index 4 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Index ...