6
6-14
C7-626 / C7-626 DP Control Systems
C79000-G7076-C626-01
Interference Suppression, Error Limits
Interference voltage
suppression for f = n
(f1
"
1 %), (f1 = interference
frequencies
)
S
Common mode
interference (V
PP
< 2.5 V)
S
Series-mode interference
(peak value of
interference < nominal
value of input range)
> 70 dB
> 40 dB
Cross-talk between the inputs
S
At 50 Hz
S
At 60 Hz
50 dB
50 dB
Basic error limit (operational
limit at 25
_
C)
1%
Data for Selecting a Sensor
Input ranges (nominal values)
/ input resistance
S
Voltage
"
10 V;
/100
k
Ω
S
Current
"
20 mA;
4 to
20 mA;
<250 Ω
<250 Ω
Permissible input voltage for
voltage input (destruction
limit)
18 V
Permissible input current for
current input (destruction
limit)
30 mA
Connection of signal sensors
S
for voltage measurement
S
for current measurement
as 4-wire transducer
Possible
Possible
Temperature compensation
Balanced by
continuous on-line
calibration
Status, Interrupts, Diagnostics
Interrupts
S
Interrupt cycle
S
Diagnostic interrupt
Yes, can be assigned
parameters
Yes, can be assigned
parameters
Diagnostic functions
S
Diagnostic information can
be read
Yes, can be assigned
parameters
Yes
Time intervals
Yes, can be assigned
parameters
Wire break detection
Can be assigned
parameters (using
software) at measuring
range 4 to 20 mA
C7 Analog Input/Output
Summary of Contents for SIMATIC C7-626
Page 18: ...1 1 6 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Product Overview ...
Page 122: ...A A 8 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 General Technical Specifications ...
Page 138: ...Glossary 10 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Glossary ...
Page 142: ...Index 4 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Index ...