C7-626 / C7-626 DP Control Systems
C79000-G7076-C626-01
6.3
Analog Input Function
This section contains
S
The characteristics of the analog input module
S
The technical specifications of the analog input module
You will learn
S
How to start up the analog input module
S
The measuring ranges provided by the analog input module
S
The parameters you can use to influence the characteristics of the analog
input module.
The following measurement types are available on the analog input module:
S
Voltage measurement
S
Current measurement
The measuring ranges are:
S
Voltage:
10 V
S
Current:
20 mA, 4 to 20 mA
For the current range 4 to 20 mA, a current of < 1.6 mA is interpreted per
software as a wire break (see Volume 2, Section 5.2).
Measuring ranges for current measurement with 4-wire transducers:
S
20 mA
S
4 to 20 mA
Overview
Available
Measurement
Types
Measuring Ranges
Wire Break Check
Measuring Ranges
for 4-Wire
Transducers