The relay contacts
8
The relay contacts can be used to report the following door states to the higher-level elevator
controller:
●
X101 (PIN3 and PIN4)
Door has reached the
"CLOSED" position.
The relay switches on when the controller has detected the
"CLOSED" position and the
pulse generator ceases to output pulses, that is the door is stationary.
Pin 3 remains
connected to Pin 4 only until the
DOOR OPEN command is issued. The relay then drops
again immediately.
●
X101 (PIN1 and PIN2)
Door has reached the
"OPEN" position.
The relay switches on when the distance of the door from the
"OPEN" position falls below
2 cm. Pin 1 and Pin 2 are then connected. If the distance falls below 2 cm again, the relay
drops immediately.
In the "Overview of operator controls", the contacts are always shown with the relay de-
energized (inactive).
WARNING
The door controller is not a safety mechanism. Therefore the relay contacts must not be
used for the elevator safety circuit.
A voltage greater than 42 V must not be connected to the relay contacts.
Elevator door drive AT12
Manual, 02/2012, A2B00086683A-04
27
Summary of Contents for SIDOOR AT12
Page 2: ......
Page 8: ...Introduction Elevator door drive AT12 8 Manual 02 2012 A2B00086683A 04 ...
Page 12: ...Definitions Elevator door drive AT12 12 Manual 02 2012 A2B00086683A 04 ...
Page 14: ...Overview of controls Elevator door drive AT12 14 Manual 02 2012 A2B00086683A 04 ...
Page 28: ...The relay contacts Elevator door drive AT12 28 Manual 02 2012 A2B00086683A 04 ...
Page 30: ...CAN Elevator door drive AT12 30 Manual 02 2012 A2B00086683A 04 ...
Page 32: ...Travel curve Elevator door drive AT12 32 Manual 02 2012 A2B00086683A 04 ...
Page 46: ...Appendix A 9 Settings record Elevator door drive AT12 46 Manual 02 2012 A2B00086683A 04 ...
Page 47: ......