Functions and device responses
5.4 Learn run button
Elevator door drive AT12
16
Manual, 02/2012, A2B00086683A-04
5.4
Learn run button
The learn run button (
S501) combines the functions of the automatic learn and test run, and
the option of opening and closing the door from the controller.
The learn and test run is activated by pressing the learn run button for more than five
seconds.
The door can be moved by pressing the learn run button briefly for between 0.1 and two
seconds.
The inputs "Open" and "Close" must not be activated:
●
First button press for between 0.1 and 2 seconds in normal or initial operation → door
opens until it reaches the "OPEN" end position, and remains stationary with the average
value of the PWM signal.
●
If the button is pressed for between 0.1 and 2 seconds again before the door has
completely opened, the door stops and remains stationary with the average value of the
PWM signal.
●
When the button is pressed again for between 0.1 and 2 seconds in normal or initial
operation → door closes until it reaches the "CLOSED" end position, and remains
stationary with the average value of the PWM signal.
●
If the button is pressed for between 0.1 and 2 seconds again before the door has
completely closed, the door stops and remains stationary with the average value of the
PWM signal.
●
The next button press opens the door again.
●
If no buttons are pressed for a period longer than 10 seconds, the next button press for
between 0.1 and 2 seconds always opens the door.
5.5
Parameter settings
The Service Tool and the Sidoor User Software offer additional setting and diagnostic
options.
The Service Tool is available as an extra, separate option.
It is connected to the
X102 connector on the controller.
The Sidoor User Software offers the easiest diagnostic option.
A PC can be connected to
X102 on the controller via the USB adapter (Software Kit
accessory).
Note
The current parameters are overwritten by the factory parameters at the end of the learn run
if the
learn run button (S501) is pressed at the same time as the supply voltage is switched
on.
If the
learn run button is pressed during operation in order to start a learn and test run, only
the door width and weight are determined. The speed of travel curve parameters, force limits
and continuous torques are retained unchanged. The maximum closing speed and the
nudge speed are limited as a function of the determined weight.
Summary of Contents for SIDOOR AT12
Page 2: ......
Page 8: ...Introduction Elevator door drive AT12 8 Manual 02 2012 A2B00086683A 04 ...
Page 12: ...Definitions Elevator door drive AT12 12 Manual 02 2012 A2B00086683A 04 ...
Page 14: ...Overview of controls Elevator door drive AT12 14 Manual 02 2012 A2B00086683A 04 ...
Page 28: ...The relay contacts Elevator door drive AT12 28 Manual 02 2012 A2B00086683A 04 ...
Page 30: ...CAN Elevator door drive AT12 30 Manual 02 2012 A2B00086683A 04 ...
Page 32: ...Travel curve Elevator door drive AT12 32 Manual 02 2012 A2B00086683A 04 ...
Page 46: ...Appendix A 9 Settings record Elevator door drive AT12 46 Manual 02 2012 A2B00086683A 04 ...
Page 47: ......