Technical specifications
11.3 Technical specifications of the electronic module
190
Manual, 08/2017, L1V30368969104A-02
Unit
3KC8 (250 to 3200 A)
Digital input
2)
Motor operator:
O position,
I position,
II position,
O position with priority,
release for remote control mode
Electronic module:
inhibition of automatic mode,
inhibition of automatic return transfer,
priority and selection of system,
test off load,
test on load,
priority for test on load,
deactivation of stabilization delay
Input delay
ms
46
Number of relay outputs
Motor unit: 4 NO
Electronic module: 1 NO 1 CO:
2A/250 V AC / 2A/24 V DC
Supplementary notes on relay
outputs
2)
Motor operator:
availability of the motor operator,
switch position I, O, II,
Electronic module:
availability of the device,
generator start/stop signal
Connections
Connecting terminals
removable / plug-in
Connectable conductor cross-
section / stranded, solid
mm
2
1.5 ... 2.5
Connectable conductor cross-
section / solid
AWG
16 ... 14
Connectable conductor cross-
section / stranded
AWG
16 ... 14
Tightening torque
Nm
0.5 ... 0.6
1)
In addition to the power loss of the motor operator
2)
You can find more information in the chapter on the functions of the inputs and outputs.
Summary of Contents for SENTRON
Page 1: ......
Page 2: ......
Page 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Page 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Page 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Page 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Page 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Page 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...