Connection
6.3 Connecting the control circuit
100
Manual, 08/2017, L1V30368969104A-02
A typical connection of sources I and II (1PH + N) to the electronic module of the 3KC8 is
shown in the circuit diagram below:
*
The F1 fuses are not required when using the 3KC9833-, 3KC9834- power supply kits.
Figure 6-87 Circuit diagram for a typical connection of the sources (1PH + N) to the electronic
module
If the power supply kit is not used, the following fuses are to be fitted:
F1
1 x 3NW6004-1
1 x 3NW7013
4 A, gG
Note
The F1 fuses must be installed as closely as possible to the tap.
Summary of Contents for SENTRON
Page 1: ......
Page 2: ......
Page 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Page 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Page 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Page 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Page 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Page 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...