Operation
7.2 Functions of the inputs and outputs
Manual, 08/2017, L1V30368969104A-02
107
Note
In the case of the 3KC8 transfer switching equipment, the inputs for the power supply are
located on the electronic module. These are described in the section titled Inputs for voltage
measurement and power supply (Page 115).
On the one hand, the motor operator is supplied with power via its inputs (3KC4 only), and
on the other, remotely operated transfer switching is enabled via these inputs.
Designation
Pin
Meaning
Explanation
Properties
Recommended
cable cross-
section
Power supply
(3KC4 only)
301
-
Power supply
208 – 277 V AC
± 20%;
45 … 65 Hz
1.5 - 2.5 mm
2
302
-
Power supply
Control inputs of
the motor opera-
tor
312
Enable Ctrl
Remote mode enabled (if closed
with 317)
Use only with
floating contacts
and supply via
pin 317
Maximum cable
length: 100 m
1.5 - 2.5 mm
2
313
OFF
Priority command for the OFF
position (if closed with input 317)
314
II
Command for transfer to position II
(if closed with input 317)
315
I
Command for transfer to position I
(if closed with input 317)
316
O
Command for transfer to position O
(if closed with input 317)
317
C
Common control terminal for inputs
312-316
NOTICE
Damage to the device
Do not connect inputs 312 to 317 to the power supply.
Summary of Contents for SENTRON
Page 1: ......
Page 2: ......
Page 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Page 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Page 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Page 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Page 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Page 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...