Connection
6.2 Connecting the main circuit
Manual, 08/2017, L1V30368969104A-02
65
6.2.5.3
Connecting current ratings 2000 A to 3200 A to the main circuit (on the load side)
The load-side connection of current ratings 2000 A to 3200 A to the main circuit is described
in the following section. Different connection variants are possible here (versions listed in the
form of a table in the section titled Copper bar connection kit (Page 49)).
WARNING
Hazardous voltage!
Ensure there is no live voltage before connecting the transfer switching equipment to the
main circuit.
NOTICE
System damage
Connect the power supply systems with phase equality.
Note
If you are using the 3KC8 transfer switching equipment, mount the corresponding
accessories for the electronic module. For information, see the section titled Connecting the
inputs and outputs of the electronic module (3KC8 only) (Page 89).
Busbar requirements
Busbars with the following minimum dimensions must be used for load-side connection:
●
Minimum copper busbar for I
th
2000 A = 3 x 100 x 5 mm
●
Minimum copper busbar for I
th
2500 A = 4 x 100 x 5 mm
●
Minimum copper busbar for I
th
3200 A = 3 x 100 x 10 mm
Summary of Contents for SENTRON
Page 1: ......
Page 2: ......
Page 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Page 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Page 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Page 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Page 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Page 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...