Accessories
9.14 Display (3KC8 only)
164
Manual, 08/2017, L1V30368969104A-02
9.14
Display (3KC8 only)
The display is intended for applications where the switch indicator and source availability
also have to be visible outside the control cabinet, e.g. on the control cabinet door. The
maximum distance of the connection is 3 m.
Figure 9-26 Display 3KC9823-0
The 3KC9823-0 display shows the following states:
●
Display of source availability
●
Indication of the switch position
●
Indication of the selected mode ("Auto")
●
Fault indicator
Current rating
Product number
250 A … 3200 A
3KC9823-0
Mounting the display
The door thickness must not exceed 20 mm to allow the display to be mounted on a cabinet
door.
1.
Release and remove the nut from the bolt thread on the rear of the display.
Figure 9-27 Display - removing the nut