Description of blocks
3.1 Diagnostics block DIA_WLVL
Library SENTRON 3WL / 3VL for SIMATIC PCS 7
20
Function Manual, 11/2008, A5E02316914A-01
Diagnostic events are assigned to maintenance status as follows:
Diagnostic event
Maintenance status QUALITY
PA_DIAG
Perform visual inspection on main contacts
Maintenance
requirement is
medium
16#68
16#0020_0000
Immediate maintenance of main contacts
Maintenance
requirement is high
16#24
16#0100_0000
3.1.9
Start-up characteristics
In OB100, the identifier for "Start up" is entered for output OMODE (OMODE=16#xx01xxxx).
3.1.10
Block parameters
The as-supplied state of the block displayed in CFC is shown in the "I/O" column: I/O name
bold = I/O is visible, normal = I/O is invisible.
I/O (parameter) Comment
Data type
Default
Type OCM
EN_DIAG
1 = Enable read diagnostic data
BOOL
FALSE
I
MODE
Parameter OMODE of DRV_WLVL
WORD
0
I
LADDR
Logical address of module
INT
0
I
DADDR
Diagnostic address of module
INT
0
I
DPA_LINK
Device connection:
0 = DP-MASTER,
1 = DP/PA-LINK
BOOL
FALSE
I
SUBN_TYP
1 = External DP interface
BOOL
FALSE
I
SUBN1_ID
ID of Primary Subnet
BYTE
16#FF
I
SUBN2_ID
ID of Redundant Subnet
BYTE
16#FF
I
RACK_NO
Rack number
BYTE
0
I
RACKF
1 = Rack failure
BOOL
FALSE
I
SUBN1ERR
1 = Slave 1 Failure
BOOL
FALSE
I
SUBN2ERR
1 = Slave 2 Failure
BOOL
FALSE
I
ACC_ID
1 = Accept new mode settings
BOOL
TRUE
IO
DIAG_REQ
1 = Read diagnostic information
BOOL
FALSE
I
QERR
1 = Error
BOOL
FALSE
O
QMODF
1 = Module Failure
BOOL
FALSE
O
QRACKF
1 = Rack failure
BOOL
FALSE
O
RACK1ERR
1 = DP slave system failure (primary)
BOOL
FALSE
O
RACK2ERR
1 = DP slave system failure (redundant)
BOOL
FALSE
O
QUALITY
Quality code of process value
BYTE
0
O
OMODE
Status MODE
DWORD
0
O