I/O (parameter)
Comment
Data type
Default
Type OCM
IN_PRO_PARA_A_OFF
DR 129: Instantaneous protection parameter
li PS A OFF
BOOL
FALSE
O
x
IN_PRO_PARA_A_NA
DR 129: Instantaneous protection parameter
li PS A not available
BOOL
TRUE
O
x
SHORT_D_PROT_A
DR 129: Short time delayed prot. parameter
lsd PS A
REAL
0.0
O
x
SHORT_D_PROT_A_QC
Quality code of SHORT_D_PROT_A
BYTE
16#80
O
SHORT_D_PROT_A_OFF
DR 129: Short time delayed prot. parameter
lsd PS A OFF
BOOL
FALSE
O
x
SHORT_D_PROT_A_NA
DR 129: Short time delayed prot. parameter
lsd PS A not available
BOOL
TRUE
O
x
T_STRIP_A
DR 129: Delay time for S-trip tsd PS A
REAL
0.0
O
x
T_STRIP_A_QC
Quality code of T_STRIP_A
BYTE
16#80
O
T_STRIP_A_OFF
DR 129: Delay time for S-trip tsd PS A OFF
BOOL
FALSE
O
x
T_STRIP_A_NA
DR 129: Delay time for S-trip tsd PS A not
available
BOOL
TRUE
O
x
E_FLT_PROT_A
DR 129: Earth fault protection parameter
lg1 PS A
REAL
0.0
O
x
E_FLT_PROT_A_QC
Quality code of E_FLT_PROT_A
BYTE
16#80
O
E_FLT_PROT_A_OFF
DR 129: Earth fault protection parameter
lg1 PS A OFF
BOOL
FALSE
O
x
E_FLT_PROT_A_NA
DR 129: Earth fault protection parameter
lg1 PS A not available
BOOL
TRUE
O
x
T_EFLT_A
DR 129: Delay time earth fault protection
tg1 PS A
REAL
0.0
O
x
T_EFLT_A_QC
Quality code of T_EFLT_A
BYTE
16#80
O
T_EFLT_A_OFF
DR 129: Delay time earth fault protection
tg1 PS A OFF
BOOL
FALSE
O
x
T_EFLT_A_NA
DR 129: Delay time earth fault protection
tg1 PS A not available
BOOL
TRUE
O
x
I2T_D_STRIP_A
DR 129: I2t curve for delayed S-trip PS A
BOOL
FALSE
O
x
I2T_D_STRIP_A_QC
Quality code of I2T_D_STRIP_A
BYTE
16#80
O
I2T_D_STRIP_A_OFF
DR 129: I2t curve for delayed S-
trip PS A OFF
BOOL
FALSE
O
x
I2T_D_STRIP_A_NA
DR 129: I2t curve for delayed S-trip PS A not
available
BOOL
TRUE
O
x
I2T_EFLT_PROT_A
DR 129: I2t curve for earth fault protection
PS A
BOOL
FALSE
O
x
I2T_EFLT_PROT_A_QC
Quality code of I2T_EFLT_PROT_A
BYTE
16#80
O
I2T_EFLT_PROT_A_OFF
DR 129: I2t curve for earth fault protection
PS A OFF
BOOL
FALSE
O
x
I2T_EFLT_PROT_A_NA
DR 129: I2t curve for earth fault protection
PS A not available
BOOL
TRUE
O
x
ZSS_ON
DR 129: ZSI on / off
BYTE
16#0
O
x
ZSS_ON_QC
Quality code of ZSS_ON
BYTE
16#80
O
ZSS_ON_OFF
DR 129: ZSI on / off OFF
BOOL
FALSE
O
x