Description of blocks
3.3 Driver module DRV_3VL
Library SENTRON 3WL / 3VL for SIMATIC PCS 7
120
Function Manual, 11/2008, A5E02316914A-01
Protect. para – protect. para tab (PROTPARA)
(1)
TL_CL_A
(2)
I2T_D_STRIP_A
(3)
OV_LD_N_A
(4)
I2T_EFLT_PROT_A
(5)
RD_DR129
(6)
T_EFLT_A
(7)
E_FLT_PROT_A
(8)
IN_PRO_PARA_A
(9)
T_STRIP_A
(10) SHORT_D_PROT_A
(11) OV_LD_A
Figure 3-34 Faceplate for protect. para view, protect. para tab
Element (parameters)
Meaning
Display when 3VL is
connected following Y-link
OC_LD_A
Overload parameter IR parameter set A (PS A)
No
TL_CL_A
Time-lag class tR PS A
No
SHORT_D_PROT_A
Short-circuit protection delayed Isd PS A
No
T_STRIP_A
Delay time for short-circuit protection tsd PS A
No
IN_PRO_PARA_A
Short-circuit protection instantaneous Isd PS A
No
E_FLT_PROT_A
Ground-fault protection Ig1 PS A
No
I2T_EFLT_PROT_A
I2t characteristic for ground-fault protection PS A
No
I2T_D_STRIP_A
I2t characteristic for delayed ground-fault protection
PS A
No
OV_LD_N_A
Overload protection neutral conductor IN PS A (WL)
No