Function Blocks
UM353-1
March
2003
3-24
An alarm status word is shown below.
A_=1 when the alarm is active
N_=1 when the alarm is Not acknowledged
E_=1 when the alarm is enabled (when the alarm is disabled the E, N, and A bits are set to 0)
OS=1 indicates that all alarms are identified as Out of Service which means that all alarms function normally but the
OS flag indicates to a higher level device that they can be ignored. OS cannot be set locally.
CC=1 indicates a configuration change has occurred. It can be reset by a write command.
AE=1 indicates an Active Event is present within the loop. It will clear when all the loop events clear.
NA will be set to 1 when events occur and at least one within the loop has not yet been acknowledged. It can be
reset to 0 which will acknowledge all events within the loop or when 0 will indicate all active events have been
acknowledged
BIT
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
AE NA CC OS E4 N4 A4 E3 N3 A3 E2 N2 A2 E1 N1 A1
0
3.2.13 AND_ - AND Logic
AND_
function blocks perform a logical AND on the three
inputs. Any unused input will be set high (1).
Input
A
AND
O1
O
utput
1
AND
AND_
ESN = 000
A
E S N
E
xec.
S
eq.
N
o.
(H)
................ 001 to 250
C
T
U
P
N
I
INPUT B
(H)
..........
loop tag.block tag.output
(
null
)
Input
B
B
B
T
U
P
N
I
INPUT C
(H)
..........
loop tag.block tag.output
(
null
)
Input
C
C
A
T
U
P
N
I
INPUT A
(H)
..........
loop tag.block tag.output
(
null
)
BLOCK DIAGRAM
A
O1
B
C
AND TRUTH TABLE
A
B
C
O
utput
1
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
AND
.
.
StockCheck.com
Summary of Contents for Moore 353
Page 2: ...S t o c k C h e c k c o m ...
Page 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Page 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Page 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Page 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Page 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Page 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Page 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...
Page 298: ...Model Designation and Specifications UM353 1 March 2003 14 16 S t o c k C h e c k c o m ...
Page 302: ...Abbreviations And Acronyms UM353 1 15 2 March 2003 S t o c k C h e c k c o m ...
Page 304: ...Warranty UM353 1 W 2 March 2003 S t o c k C h e c k c o m ...