Model Designation and Specifications
UM353-1
March
2003
14-2
TABLE 14.1 Moore 353 Model Designation*
353
P
ROCESS
A
UTOMATION
C
ONTROLLER
MPU Controller Board
A
120/240 Vac (85-264 Vac), 47-63 Hz.
D
24 Vdc, +20%, -15%
Mounting Case
1
Case with 26 Terminals; not expandable to 52 terminals -
Discontinued
2
Case with 52 Terminals (Black Side Entry Connectors) -
Discontinued
4
Case with 52 Terminals (Gray or Green Direct Entry Connectors) and Ethernet Connector
5
High Shock and Vibration Case with Ethernet Connector (requires Electrical Approval “N Not Required”)
Operator’s Display Panel
(Display Assembly)
F
Fixed Analog & Digital Displays
I/O Expansion
N
Not
Required
1
Local I/O Expander (e.g., T/C, RTD, Frequency, Relay)
Option Board A-1, Remote I/O Communications
N
Not
Required
L
LonWorks
Protocol
Option Board A-2
N
Not Required
Option Board B-1, Network Communications
N
Not
Required
E
Ethernet
L
Local Instrument Link (LIL)
Option Board B-2, Real Time Clock/Configuration Backup
N
Not
Required
R
Removable Configuration Board (RCB) -
Discontinued
T
Real Time Clock/Configuration Backup Board (RTC/CB)
Modification Options
N
Not
Required
X
Controller Modified as detailed in order bill of material
Reserved for Future Use
N
Reserved for Future Use
Design
Level
A
Design Level A
Electrical
Approval
N
Not Required
4
FM/CSA Division 2 Class 1 Groups A, B, C & D suitable for
non-incendive (CE compliant)
W
FM/CSA Division 2 Class 1 Groups A, B, C & D suitable for
non-incendive (CE compliant and ABS approved)
X
FM/CSA Division 2 Class 1 Groups A, B, C & D suitable for
non-incendive
353A 4 F N N N N N N N
A
N
Sample Model No.
Contact Siemens Energy & Automation, Process Instrumentation for the latest model designation information, availability of
some options, and current electrical approvals.
Always refer to the labels on the controller case for approvals and
certifications.
StockCheck.com
Summary of Contents for Moore 353
Page 2: ...S t o c k C h e c k c o m ...
Page 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Page 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Page 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Page 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Page 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Page 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Page 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...
Page 298: ...Model Designation and Specifications UM353 1 March 2003 14 16 S t o c k C h e c k c o m ...
Page 302: ...Abbreviations And Acronyms UM353 1 15 2 March 2003 S t o c k C h e c k c o m ...
Page 304: ...Warranty UM353 1 W 2 March 2003 S t o c k C h e c k c o m ...