Appendix D: Menu Parameters
Siemens Power Transmission & Distribution, Inc.
61
EXAMPLE 1 (ref: Table D.3)
In Figure D.3 below, U6 is to the left of E2. If your regula-
tor nameplate looks like this, the proper specification is
Utility Pol:NORM.
Figure D.3
U6 to the Left of E2
EXAMPLE 2 (ref: Table D.3)
In Figure D.4 below, U6 is to the right of E2. If your regula-
tor nameplate looks like this, the proper specification is
Utility Pol:REV.
Figure D.4
U6 to the Right of E2
D.3.2
Three-Phase Regulators
Three-phase regulators may have either one or multiple
utility windings.
D.3.2.1 Single Utility Winding
A single utility winding provides power for the control, the
motor and the cooling fan. This utility winding may have
the polarity mark at the Un — Ux terminals or at the U5
terminal, as shown in the examples of Figure D.5.
Figure D.5
Three-Phase Regulator with a Single Utility
Winding
To determine whether the polarity is ‘Normal’ or ‘Reverse,’
examine the connection table and schematic diagram.
•
If U2 is connected to a “U” terminal which is to the
left of E2, then UtilityPol:NORM (see Figure D.6).
•
If U2 is connected to a “U” terminal which is to the
right of E2, then UtilityPol:REV (see Figure D.7).
U6
E2
U3
U4
U9
U5 U7 U8
U9
E2 U3
U7
U8
U6
U4 U5
U3
U5
E2
E2
U5
U3
Summary of Contents for MJ-XL