4
Setting Up the MJ-XL Control Panel
18
Siemens Power Transmission & Distribution, Inc.
Figure 4.2
Typical Siemens Regulator Nameplate for ANSI Type A (Straight) regulator
Note: Items are not highlighted on actual nameplate.
Figure 4.3
Typical Siemens Regulator Nameplate for ANSI Type B (Inverted) Regulator
Note: Items are not highlighted on actual nameplate.
SIEMENS
5/8% Step-Voltage Regulator
Serial No.
Single Phase Type JFR
60 Hz
55 C Rise
95 BIL
Class OA
167 kVA 7620 volts 10% in 32 - 5/8% Steps
219 Amps
Insulating Fluid : ASTM D-3487 Type II Mineral Oil Less than 1 ppm PCB
Untanking Hgt = 131 in.
Untanking Wgt = 1126 lbs.
Oil = 91 gals.
Total Wgt = 2100 lbs.
Control diag : 21-203-980-414
Nameplate
: 21-115-907-435
% Regulation
7970 V
7620 V
7200 V
Max Amps
210
219
232
230
241
255
251
263
278
283
296
313
335
351
371
10
8
7
3/4
1/2
1/4
6
5
Load
Volts
10%
7970
7620
7200
P3 - 120 V
P4 -
120 V
P5 - 120 V
20
20
20
20
20
20
U3
117
U4
125
U4
118
120
120
120
* Volt Tran
Sec conn
P2 to
P14 to
P to
Contr
Volts
Control
Panel
* Aux volts
Motor Conn
U2 to
Volts
Copper conductor in shunt winding.
Aluminum conductor in series winding.
Tank withstands full vacuum
DATE:
CT sec conn C2 to C3
21-115-907-010
U7 U6 U5 U4
P4 P3
P5
E3
U3 E2
E1
CT
AMPS
250 : 0.2
C3
8765 43
B
A
K
M
S
LOAD
L
SL
SOURCE
0
21
ANSI TYPE "A"
TapChngr SIEMENS
I FullLoad 219
Type STRAIGHT
CTratio 250:0.2
Utility Pol NORM
(E2 to right of
U Terminals)
Tap Changer
Preventive
Autotransformer
Tap Changer
Reversing Switch
P2PT: 7620 : 120
Basis volts 120
U2PT: 7620 : 125
Do not by-pass unless on neutral and control switch on panel is off
See instruction book before placing in service.
S i e m e n s P o w e r T r a n s m i s s i o n & D i t r i b u t i o n , I n c .
J a c k s o n , M S
M a d e i n U S A
SIEMENS
5/8% Step-Voltage Regulator
Serial No.
Single Phase Type JFR
60 Hz
55 C Rise
95 BIL
Class 0A
76.2 kVA 7620 volts 10% in 32 - 5/8% Steps
100 Amps
Insulating Fluid : ASTM D-3487 Type II Mineral Oil Less than 1 ppm PCB
Untanking Hgt = 117 in.
Untanking Wgt = 682 lbs.
Oil = 64 gals.
Total Wgt = 1431 lbs.
Control diag : 21-203-980-468
Nameplate
: 21-115-905-464
% Regulation
7620 V Amps
100
110
120
135
160
10
8
7
3/4
1/2
1/4
6
5
Load
Volts
10%
8000
7620
7200
5000
4330
2500
122 V
122 V
115 V
122 V
122 V
118 V
P2-P3
P2-P4
P2-P4
P2-P5
P2-P6
P2-P7
21
21
25
23
23
27
23
23
20
20
20
20
120 V
120 V
120 V
125 V
125 V
125 V
Control & Motor
Control Panel Conn
Volts
E-P2
Connect
*
PA
to
P14A
to
Control
Volts
Copper conductor in shunt winding.
Aluminum conductor in series winding.
Tank withstands full vacuum
DATE:
Do not by-pass unless on neutral and control switch on panel is off
See instruction book before placing in service.
CT sec conn C2 to C3
21-115905-002
P7
P6
P5
P4
P3
E2
E1
CT
AMPS
100 : 0.2
C3
87654 3
A
B
M
K
S
LOAD
L
SL
SOURCE
0
21
ANSI TYPE "B"
TapChngr SIEMENS
I FullLoad 100
Type INVERTED
CTratio 100:0.2
U2PT: 7620: 122
(NO P2PT:)
Basis volts 120
Utility Pol NORM
(E2 to right of
P Terminals)
Tap Changer
Preventive
Autotransformer
Tap Changer
Reversing Switch
S i e m e n s P o w e r Tr a n s m i s s i o n & D i t r i b u t i o n , I n c .
J a c k s o n , M S
M a d e i n U S A
Summary of Contents for MJ-XL
Page 85: ......