4
Setting Up the MJ-XL Control Panel
16
Siemens Power Transmission & Distribution, Inc.
4 Setting Up the MJ-X
L
Control Panel
4.1
Setup— Overview
MJ-X
L
Control Panel setup procedures allow you to cus-
tomize the control panel to your needs and to the environ-
ment in which it is installed. You can describe specific
regulator parameters and power-flow conditions, and
define automatic-mode operation. Previous generation
controllers used dip switch settings and jumpers for this
purpose. With the MJ-X
L
Control Panel, simply use front
panel touch-keys and the display screen to define the
operating environment. Also, the MJ-X
L
communication
facilities in conjunction with the MJXplorer software can
be used to set up the MJ-X
L
Control Panel.
The setup process for the MJ-X
L
Control Panel consists of
several steps:
Configuration
In this step, use the <
CONFIGURE
> Menu to describe
the regulator and the power distribution system.
Setpoints
In this step, use the <
REGULATOR
> Menu to define
Automatic Mode setpoints (voltage level, bandwidth, time
delay, etc.).
Logging Requirements
In this step, use the <
LOG SETUP
> Menu to define data
logging requirements (what values you want logged, how
often, under what conditions, etc.).
Security Definition
In this step, use the <
PASSWORD
> Menu to define pass-
words and to activate security protection.
Communications Definition
In this step, use the <
COMMUNICATIONS
> Menu to
define communications parameters (baud rate, unit
address, etc.).
This chapter describes each of the setup parameters, and
explains how they are defined. Chapter 7 contains addi-
tional detail and background information to help you make
the proper selections.
Table 4.1
The <
CONFIGURE
> Menu
DATA ITEM
DESCRIPTION
VALID INPUTS
DEFAULT
INC
TapChngr
Tap Changer Type
SIEMENS, GE, LTC, LTC.5, COOP SD, or COOP DD
SIEMENS
- - -
Type
Regulator type
STRAIGHT or INVERTED
STRAIGHT
- - -
Syst
System wiring configuration
WYE, DELTA LAG, DELTA LEAD
WYE
- - -
DeltaPwr
Delta power configuration
OPEN or CLOSED
OPEN
- - -
Utility Pol
Utility winding polarity
NORM, REV
NORM
- - -
U2 PT
Utility winding turns ratio
1500 to 65,500:100 to 150
7200:120
1 Volt
P2 PT
Potential Transformer turns ratio
1500 to 65,500:100 to 150
7200:120
1 Volt
CTratio
Current Transformer turns ratio
50 to 7200:0.0 to 9.5
200:0.2
1:0.1
Meter Volts
Transformer side used for Metering
SEC, PRI
SEC
- - -
I Threshold %
Tap change minimum current
0% to 10%
1%
1%
I Shift
Current shift for reverse power flow
0° to 359°
0°
1°
I Load Max
Max. Load Current (for Overcurrent)
0% to 350%
350%
1%
I FullLoad
Regulating Device Full Load Rating
50 to 7200
350
1 Amp
PwrFlow
Power flow modes
F LOCK, R LOCK, IDLE R, BI-DIR, NEUT R, CO-GEN
F LOCK
- - -
PT Threshold
Tap change low voltage limit
0 to 134
90
- - -
Time
Time of day
HH:MM:SSA/P
- - -
- - -
Date
Date
NN/NN/NN
- - -
- - -
Format
Date format
MO/DA/YR or DA/MO/YR
MO/DA/YR
- - -
Dmd Type
Method for determining Demand
THERMAL or WINDOW
THERMAL
- - -
Dmd Time
Demand Period length (minutes)
1 to 999
30
1 Minute
DmdSubperiods
Number of Demand subperiods
1 to 99 (For Sliding Window mode only)
6
1
Reset Min/Max?
Reset all min/max readings
N or Y
N
- - -
Min/Max t.o.
Min/Max display timeout (seconds)
1 to 99
15
1 Second
Screen t.o.
Return to <
METER
> Menu (min.)
1 to 99
5
1 Minute
Function t.o.
Return to previous Menu item
1 to 99
10
1 Second
Basis volts
Controller nominal voltage level
115, 120, or 125v
120
- - -
R Limit
Raise Limit (for Alert Only)
10, 8¾ , 7½ , 6¼ , 5
10
- - -
L Limit
Lower Limit (for Alert Only)
10, 8¾ , 7½ , 6¼ , 5
10
- - -
Tap Alert
Enable or disable tap alerts
ENABLE or DISABLE
ENABLE
- - -
TapPosHold
Hold tap position value indefinitely
PERM. or TEMP.
TEMP.
- - -
Vers
Microprocessor software version
NN.NNNN
- - -
- - -
Memo1
User-supplied text
Up to 10 Characters
All blanks
- - -
Memo2
User-supplied text
Up to 10 Characters
All blanks
- - -