Using the MJ-XL Operator Panel and Controls
Siemens Power Transmission & Distribution, Inc.
11
Power and Motor Control Terminal Contacts
A simplified schematic drawing of the power and motor control terminal connections is shown in Figure 2.3 below
.
Figure 2.3
Simplified Schematic of “Terminal” Remote Control Connections
Power Switch
On
External
PDS-U2
External
Source
(Line)
12
12
12
11
11
11
10
10
10
9
9
9
9
8
7
5
5
5
4
4
4
3
3
3
6
6
6
7
7
7
8
8
8
9
PDS-J
PDS-K
10
U
P2B
P2B
P2B
P2B
P3A
P3A
P3A
P2B
P2B
P2B
P2B
P2B
P2B
P2A
P2A
U
U
U6
U6
U6
U6
U6
U6
U7
U7
U7
REM-STAT
R/M Com
MAN-STAT
U-REM
U-REM
U-REM
Relay
Contacts
Open - Disable
Close - Enable
T.B.
Remote
Raise
Relay
Contacts
T.B.
Remote
Lower
J22
J22
J22
J21
J21
J21
U-REM
U-REM
U-REM
K22
K22
K22
K21
K21
K21
Remote/Auto/Manual
Switch
Manual
Tap
Raise/Lower
Switch
Manual
Remote
Raise
Off
Lower
"K" Current Sense
"J" Current Sense
Status
Outputs
Automatic
"Raise"
Relay*
K4
Automatic
"Lower"
Relay*
K5
Motor
Power
Control
Relay
K7
Connections for
External Motor Power
Connections for "Terminal Block" (T.B.) Remote Control
T.B. Remote Control for
R/A/M Switch in Remote
T.B. Remote Enable/Disable of
Automatic Operations
Connections for
External Motor Power
(Automatic Only)
External Power
(or connect
Relay between
U and U6)
External Power
(or connect
Relay between
U6 and U7)
Status of Remote/Auto/Manual Switch
REM to COM
Closed
Open
Open
Switch Position
Remote
Auto
Manual
MAN to COM
Open
Open
Closed
*Auto relays disabled when R/A/M
switch is in Manual position
Note: The dotted-lineconnections between terminals
represent the default (factory installed) jumpers.