Siemens Industry, Inc.
98
CustomTap
100% configurable, all <Diagnostic > menu configurations unlocked
Default Values
Due to storage limitations, once a tap changer is selected, the default values are set. The MJ-XL has no
method of recalling the previous value(s) for another changer type. In short, once the changer type is
changed the modified Configuration will be wiped from memory and replaced with the default values. The
default values are as follows:
Parameter
Siemens
GE
COOP SD
COOP DD
LTC (D-Star)
LTC .5
R/L On Time:
8.0
8.0
8.0
0.5
5.0
0.5
R/L Off Time:
0.0
3.0
3.0
3.0
2.0
3.0
Tap Change T/O:
0.0
3.0
3.0
3.0
3.0
3.0
TapIn Signal:
U10
U10
HS
HS
U10
U10
TapInType:
TOGGLE
PULSE
PULSE
PULSE
PULSE
PULSE
TapInPulse:
0.00
0.02
0.02
0.60
1.00
0.6
PreTapTime:
0.2
0.5
0.5
0.5
0.2
0.5
PostTapTime:
1.2
0.5
0.5
0.5
1.2
0.5
Neutral In:
U12
U12
U112
U112
NONE
NONE
NeutralCount:
1
1
1
1
1
1