Siemens Industry, Inc.
88
Configuring the MJ- Control Panel
1)
For “Util Winding Pol”, select “Normal”
2)
For “Tap Changer Type”, select “GE”
3)
For “Regulator Type”, select “Inverted” (regardless of regulator’s actual type)
4)
Enter the control winding voltage ratio in “P2PT” screen and the “U2PT” screen.
Note: The control winding (E) voltage, transformer voltage, CT ratio, “I Full Load,”
“I Load Max,” and other parameters may be read from the regulator nameplate.